Setpoint Settings - salmson SIE BV Serie Instalacion Y Puesta En Servicio

Ocultar thumbs Ver también para SIE BV Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

No.
Designation
1
+10 V DC
2
0...10 V/0...20 mA
3
0...10 V/0...20 mA
4
+24 V DC
5
+24 V DC
6
Not used
7
Earth (GND)
8
RUN
9
"+" button
10
Operating mode
11
+24 V DC
12
Earth (GND)
13
0...10 V
14
Not used
15
Earth (GND)
16
"–" button
17
Reset
18
Ext. off
19
Not used
20
RUN
21
RUN
22
RUN
31-32-
SBM
33
41-42-
SSM
43
8.2

Setpoint settings

Type with differential pressure
sensor:
Installation and operating instructions SIE...BV/DIE...BV/PBE...BV
Overview and functions of the connection terminals for signal
inputs and outputs
Input/output
Output
Analogue input
Analogue input
Output
Output
Output
Output
Digital input
Digital input
Digital input
Output
Output
Analogue output
Analogue output
Output
Digital input
Digital input
Digital input
Digital input
Digital output
Digital output
Digital input
Output
Output
The operating mode and the setpoint signal are set via the bridges on
the signal connection terminals (see Section 7.3.1).
NOTE
With DIE...BV, conversion is done on the master module only.
Button
Pressure controlled operation (Δp-c):
The actual value of the pressure in the system is always compared to
the defined setpoint and the speed of the pump is adjusted accord-
ingly. The actual value is transferred to the control via the corre-
sponding differential pressure sensor "0-10 V" (0 V = 0 bar).
Setting for pressure controlled operation: (factory setting)
Bridge between terminal 5 and terminal 10 closed (Fig. 5).
Function
Factory-set
For external voltage/current signal
Input signal for differential pressure sensor
For external sensor/consumer (DDS)
Operating mode supply setting
For signal inputs 0...10 V/0...20 mA
Factory-set
Factory-set
Δp-c control or n-const manual control mode
Factory-set
Factory-set
Double pump control
For signal inputs 0...10 V/0...20 mA
Factory-set
Factory-set
External Off function
Factory-set
Fault-actuated switchover
Fault-actuated switchover
Collective run signal
Collective fault signal
The setpoint can be set as pressure setpoint (H
speed (n
) and increased or reduced using the two
s
buttons.
H
: Pressure setpoint in % of the differential pressure
s
sensor's final value (applies to pressure controlled
operation only); a pressure gauge is required to
adjust the setpoint!
n
: Target speed according to the frequency
s
12.5...50 Hz (applies to manual control mode).
English
) or as
s
45

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Die bv serie

Tabla de contenido