FASTENING THE BURNER TO THE BOILER
MOD. BT 75 DSG/3V - BT 100 DSG - BT 120 DSG/3V
REMARK: When tightening the flange, it is important to do it evenly so that the inner faces are parallel
between them. Since the locking system is highly efficient, do not tighten the nuts too much.During
this operation (tightening of the flange locking nuts) keep the body of the burner lifted so that the
combustion head is kept in a horizontal position.

APPLICATION OF THE BURNER TO BOILER

MOD. BT 40 DSG - BT 55 DSG - BT 180 DSG/3V
1 Boiler plate
2 Flange with insulating materials
3 Seam with insulating materials
4 Burner securing flange
5 Stud bolts, washers and nuts for fastening to the boiler
6 Nuts screws and washers to fasten flange to the sleeve
COMBUSTION HEAD ASSEMBLY
To put in place insulation flange 2, which must be posi-
tioned between the burner and the plate of boiler 1, the
end of the combustion head must first be removed.
a) Adjust position of connector flange 4 by loosening
screws 6 so that the combustion head penetrates into
the combustion chamber the amount recommended
by the generator's manufacturer.
b) Position seal insulation  on the tube unit.
c) Fasten the combustion head assembly to the boiler 1 using the stud bolts, washers
and the nuts provided 5.
d) With suitable material, completely seal the space between the tube unit of the
burner and the hole on the refractory plate inside the boiler door.
ENGLISH
0 / 98
00060807_200709
N° 000290
REV. 25/10/2000
1) Boiler plate
2) Insulating flanges
3) Burner mounting flanges
) Flexible collar
5) Stud bolt
6) Locking nut with washer
7) Nut and washer for fastening the
first flange