Fault
The display shows
"
Not enough UV. Add.
The display shows
"
Not enough oil. Add.
The display shows
"
Max. filling time
exceeded! Continue?
The display shows
"
Ext. tank empty or closed
"
valve! Check!
The display shows
"
Change the equipment
drier filter! Continue?
The display shows
"
Change the vacuum
"
pump oil. Go on?
The display shows
"
Printer not in line.
"
Carry on?
The display shows
"
"
Error 01
The display shows
"
"
Error 02
The display shows
"
"
Error 05
(ASC2000RPA only)
AirConServiceCenter
Cause
This message appears
"
during the filling process
if there is not enough UV
additive in the container
to finish the process.
This message appears
"
during the filling process if
there is not enough fresh
oil in the container to finish
the process.
This message appears
during the filling process if
the set amount of refrigerant
"
cannot be filled.
This message appears at
the start or during the filling
of the internal refrigerant
container if the set refrigerant
quantity cannot be attained.
This message appears
when you switch on the
AirConServiceCenter.
"
This message appears
when you switch on the
AirConServiceCenter.
This message indicates a
printer fault.
Refrigerant was put in before
draining was completed.
The air conditioning system
is leaking. There is still
refrigerant in the air
conditioning system.
Pressure too low at
connection (8) for
nitrogen bottle.
Troubleshooting
Remedy
Fill the UV additive container.
ASC1000: make sure the
scales and container can
move freely.
Top up the fresh oil container
with a suitable oil type.
ASC1000: make sure the
scales and container can
move freely.
Check that
AirConServiceCenter
connections are not blocked.
Check if the external
refrigerant container
still contains enough
refrigerant or if the valves
of the external refrigerant
container are open.
Change the internal filter
as soon as possible
(see page 94). To proceed,
press Enter for 3 secs.
Change the vacuum pump
oil as soon as possible
(see page 98). To proceed,
press Enter for 3 secs.
Check if there is paper in
the printer.
Check if the printer is
switched on (yellow LED
must light up constantly).
Check that the cover is
closed properly.
Repeat the draining
procedure; do not
interrupt it this time.
Fix the leak.
Set the pressure regulator
on the external nitrogen
bottle to max. 12 bar.
Replace the bottle if it
is empty.
105