6. Once the oil has been completely drained from the pump housing,
screw the oil drain plug (J) back in.
7. Top up with new vacuum pump oil to the middle of the sight glass (H)
and screw the oil filler plug (G) back in.
8. Put the front panel and control panel back on and reconnect the
power plug.
After finishing the service tasks, you must delete the service messages
(counter reset). To do this, switch to "Other selections - Service" and
enter the password "7782". First, the totals appear (since initial start-up -
these cannot be reset). To return to the values which can be reset,
press the cursor key
8.6
Extracting contaminated refrigerant
Should the analysis (ASC2000RPA only) determine that the extracted
refrigerant contains refrigerants other than R 134a, the AirCon Service
Center will abort the extraction process and the contaminated refrigerant
will remain in the air conditioning system. In this case, the contaminated
refrigerant needs to be pumped from the service hoses of the AirCon
Service Center and the air conditioning system using the refrigerant
draining station, WAECO item number 8885200059.
1. Disconnect service hoses (11) and (12) from the air conditioning
system.
2. Use the refrigerant draining station, WAECO item number
8885200059, to empty the service hoses (11) and (12).
See the operating manual for instructions.
AirConServiceCenter
H
I
four times. Follow the instructions on the display.
G
J
Service tasks
99