Service tasks
8
Service tasks
8.1
Calibrating the scales
(only ASC2000, ASC2000RPA and ASC3000)
In order for the oil quantities and the UV additive to be measured correctly,
the zero point of the scales must be checked regularly and reset if necessary.
Resetting is necessary:
If the quantity in a container deviates by more than 10ml from the
target value
If the AirConServiceCenter has been shaken, for example during
transport on bumpy roads
Every four to six weeks
1. In standby mode, use the cursor keys
"Other selections":
2. Press ENTER to confirm.
3. Use the cursor keys
4. A request to remove the container from the scale appears:
92
Short selection
Free selection
Other selections
ENTER-OK
or
to select "Reset Scales":
Int. vessel filling
Fluxing
Reset Scales.
Service.
Scale
empty ?
ENTER-OK STOP-EXIT
or
to select
AirConServiceCenter