6.8
Filling up the internal refrigerant container
When the AirConServiceCenter is started for the first time, the internal
refrigerant container must be filled from an external refrigerant tank with
at least 5000g of refrigerant.
Note the instructions on the refrigerant vessels.
The current levels are shown in the info menu (see "Opening the info
menu" on page 74).
There are three different types of refrigerant vessel available:
Refrigerant vessels without rising pipe (for example,
WAECO item no. 8887100002)
These refrigerant vessels have one connection.
When filling the AirConServiceCenter, the connection must be at the
bottom (container turned upside down).
Refrigerant containers with a rising pipe
These refrigerant vessels have one connection.
When filling the AirConServiceCenter, the connection must be at the
top (container upright).
Refrigerant vessels with rising pipe:
These refrigerant vessels have two connections. To fill the
AirConServiceCenter, use the connection labelled L (= liquid).
To fill the AirConServiceCenter, the connection must be at the top
(container upright).
1. In standby mode, use the cursor keys
"Other selections":
2. Press ENTER to confirm.
3. Use the cursor keys
4. Press ENTER to confirm.
5. Follow the instructions in the display.
AirConServiceCenter
Short selection
Free selection
Other selections
ENTER-OK
or
to select "Int. vessel filling":
Int. vessel filling
Fluxing
Reset Scales.
Service.
First start-up
or
to select
73