Descargar Imprimir esta página

Waeco AirCon Service Center Instrucciones De Uso página 89

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8. Deselect "Filling phase" with No (the chosen setting flashes) and
press ENTER to confirm.
9. Select "Process start" with ENTER.
10. Disconnect the system components which cannot be flushed from the
refrigerant circuit. These components are, for example:
- Compressor
- Line filter
- Fixed choke
- Collection containers
- Filter drying units
- Expansion valve
11. Connect the components to be flushed to the service ports (14)
and (15) of the AirConServiceCenter using special adapters to form
a flushing circuit.
12. In standby mode, use the cursor keys
"Other selections":
13. Press ENTER to confirm.
14. Use the cursor keys
15. If necessary, enter the desired data with the keypad (7) and press
ENTER to confirm.
If you do not want to enter any data here, press ENTER to advance to
the next program step.
16. Use the cursor keys
conditioning system or just individual components:
17. Press ENTER to confirm.
18. Follow the instructions in the display.
AirConServiceCenter
Short selection
Free selection
Other selections
ENTER-OK
or
to select "Fluxing":
Fluxing
Reset Scales.
Service.
ENTER-OK STOP-EXIT
or
to select whether to flush the entire air
Full fluxing
Fast fluxing
ENTER-OK STOP-EXIT
Operation
or
to select
89

Publicidad

loading

Este manual también es adecuado para:

Asc 1000Asc 2000Asc 2000 rpaAsc 3000