BTL AK _ A00- _ _ _ _ -C11WH120-000C51-001
Magnetostrictive Linear Position Sensor – Rod Style
5
Installation and connection
5.1
Preparing for installation
5.1.1
Fastening the connection housing
For secure fastening the connection housing of the BTL
must be fastened using a support, e.g. mounting bracket
(not included in scope of delivery) with two cylinder screws
(ISO 4762, M4 × 20) (torque: 2.5 Nm).
Prepare fastening
16
50.6
Fig. 5-1:
Dimensions for fastening (example)
10
english
5.1.2
Installation variants
a) Installation in non-magnetizable material
We recommend using non-magnetizable material to mount
the BTL and magnet.
Non-magnetizable material
Magnet
min. Ø D2 = Minimum bore diameter (see Tab. 5-1)
1)
Fig. 5-2:
Installation in non-magnetizable material
b) Installation in magnetizable material
If using magnetizable material, the BTL must be protected
against magnetic interference through suitable measures
(e.g. spacer ring made of non-magnetizable material, a
suitable distance from strong external magnetic fields).
Defined minimum distances refer to a sensor
measuring length of 930 mm, 1230 mm and
1830 mm must be viewed differently for other
measuring lengths / installation situations.
Spacer ring made of
non-magnetizable
material
Spacer ring made of non-
magnetizable material
min. Ø D2 = Minimum bore diameter (see Tab. 5-1)
1)
Fig. 5-3:
Installation in magnetizable material
Magnet
15
8
Magnet