Wiring iDock Controller to LiftMaster
Maxum Operator
To prevent possible SERIOUS INJURY or DEATH:
ALL Maintenance or servicing MUST be performed by a trained door systems technician.
Disconnect electric power (including battery backup if provided) BEFORE performing ANY adjustments or
maintenance.
Do NOT reconnect electrical power until instructed to do so.
An accessory providing the door state via output relays is required for the commercial door operator. If your machine
is not equipped with the relay board accessory, part number AUXREL will be needed. See the instructions supplied with
the kit for reference:
Reference Image #1
Set Relay 2 dip switches to Off, Off, On
Set Relay 1 dip switches to Off, On, Off
The expansion board and relay adapter board provide Normally Open (N.O.) and Normally Closed (N.C.) relay contacts
to control extrenal devices, for connection of Class 2, low voltage (42 Vdc [34 Vac] max 5 Amps) power sources only.
Function of relay contact activation determined by switch settings.
SWITCH SETTINGS
AUX RELAY
SETTING
1
Off (no
OFF
feature
selected)
Open Limit
OFF
Switch
Closed Limit
OFF
Switch
Gate Motion
OFF
AUX RELAY 1
2
3
OFF
OFF
Relay always off. Use this Aux Relay setting to conserve battery power.
OFF
ON
Energizes at open limit. Use with SAMS (Sequenced Access Management
System, jointly with barrier gate).
ON
OFF
Energizes when not at close limit. For an additional audible or visual display,
connect an external light (low voltage).
ON
ON
Energizes when motor is on (gate in motion). For an additional sudible or
visual display, connect an external buzzer or light (low voltage).
 WARNING
49