Parameter
P204
Load Factory Setting
P206
Auto-Reset Time
P215
Keypad Copy Function
Description / Notes
Programs all parameters to the standard factory default, when P204=5.
The parameters P000 and P295 are not changed when the factory default parameters
are loaded through P204=5.
When any fault is detected, excepting E10, E24, E29, E31 and E67, the Soft-Starter
SSW-05 can cause an automatic reset after the time programmed at P206 has elapsed
If after an "auto-reset" the same fault is repeated three times consecutively, the Auto-
Reset function will be disabled. A fault is considered consecutive if it happens again
within 30 second after an auto-reset has been executed.
This is fault is repeated four times consecutively, it will be displayed permanently and
the Soft-Starter will be disabled.
Auto-Reset Enable/Disable is executed through the Dip Switch (Man Auto) or by means
of P106 and P220.
Note: For motor overload and thyristor overload there is a specific algorithm for
the automatic reset time.
The keypad copy function is used to transfer the content of the parameters from one
SSW to another.
Note: The Keypad Copy Function is only available when using HMI-SSW05-RS.
P215
Action
0
Copy
1
(SSW keypad)
Paste
2
(keypadSSW)
Procedure is as follows:
1. Connect the keypad (HMI-SSW05-RS) to the SSW from which the parameters willl
be copied (SSW A - source SSW).
2. Set P215=1 (copy) to transfer the parameter values from the SSW A to the keypad.
Press
key. During running of the Copy Function, display will show
P215 resets automatically to 0 (Off) after transfer has been completed.
3. Disconnect the keypad from the SSW (A).
4. Connect the same keypad to the SSW to which the parameters will be transferred
(SSW B - target SSW).
5. Set P215=2 (paste) to transfer the content of the of the keypad (EEPROM has the
SSW A parameters) to SSW B.
Press the
key. While the keypad is running the paste function, the display
shows
, an abbreviation for paste. When P215 returns to 0, the parameter
transfer has been concluded. Now SSWs A and B will have the same parameter
values. To copy the parameter content of the SSW A to other SSW(s), repeat steps
4 to 5 above.
English-28
Off
Transfers the actual parameter values
of the SSW to non volatile memory
(EEPROM) of the HMI-SSW05-RS
keypad. The actual SSW parameters
are not changed.
Transfers the content of the non volatile
memory of the keypad (EEPROM) to
the SSW parameters.
Notes
-
.