Installation and Operation Manual - SSW-05 Plus
21. ERROR CODE AND DESCRIPTION (FOR SERIAL COMMUNICATION / HMI-SSW05-RS):
Display
E03
Phase loss
E05
Output overload (Ixt function)
E06
External fault
E10
Error in the copy function
E2x
Serial communication error
E22
Longitudinal parity fault
E24
Parameterization fault
E25
Variable or parameter not existing
E26
Expected value out of the allowed limits
E27
Writing attempt in a read only variable or logical control disabled
E29
Error of the cyclic serial communication interrupted
E31
Keypad connection fault
E63
Locked rotor
E64
Thyristor overload
E65
Immediate Undercurrent
E66
Overcurrent
E67
Incorrect phase sequence
E70
Undervoltage in the control supply
E71
Internal By-pass relay contact is open
E72
Overcurrent before the By-pass
E73
Overcurrent of the SSW-05 By-pass relay
E75
Frequency out of tolerance
22. DETAILED PARAMETER DESCRIPTION (FOR SERIAL COMMUNICATION/HMI-SSW05-RS):
Parameter
Description / Notes
P000
Access Parameter
P002
Motor Current Indication
(%)
P003
Motor Current Indication
(A)
P023
Software Version
P030
R Current Phase
P031
S Current Phase
P032
T Current Phase
P050
Status Indication of the
Motor Thermal Protection
P101
Initial Voltage (%Un)
Description
Releases the access to change the parameter values.
The password is 5.
Indicates the motor current in percent (%) of nominal current.
Indicates the motor current directly in Amps.
Is necessary to program P295 correctly. This is important in the correct indication
value in amperes
Indicates the version of the software installed in the CPU.
It indicates the current of the R Phase.
Accuracy of ± 10% @ 1xIn of the SSW-05.
It indicates the current of the S Phase.
Accuracy of ± 10% @ 1xIn of the SSW-05.
It indicates the current of the T Phase.
The indicated value is estimated from the instantaneous current of the R and S Phases.
Indicates in percentage the status of the thermal motor protection (0 ... 250). 250 is
the point where the thermal motor protection trips, E05.
It sets the start voltage (%Un) that will be applied to the motor according to Figure 22.1.
When P220 = 0, the parameter content indicates the value that has been set through
the trimpot. When the trimpot has been set to the maximum value, the value indicated
at the Parameter may be lower than expected. This is due to mechanical limits
variations. The parameter content cannot be changed through the keypad when
P220 = 0.
With P220=1, the content of the parameter indicates the value programmed through
the serial communication or HMI.
English-24