Installation protocol

Note! The results for the following control points. For values note the value in the result column, else a tick will suf-
fice if the point has been preformed or considered. If a value is outside the limit or a result is wrong/ missing this
must be rectified before initial start-up and normal operation.
Correct limits or results can be seen within the parenthesis .
FlexFilter EX No
Control points
1. Application requirements Limits?
Installation Area classification (22 or none)
Material: See the product identification plate.
Material: See the product identification plate.
Material Kst: See the product identification plate.
Material Pmax: See the product identification plate.
Material chemical / thermal reaction risk ( No)
2. Delivery control
Missing components
Transport damage
3. Pre installation
Foundation - Traction forces
Foundation - Wind load
Foundation - Total weight
Foundation - Anchor bolts
Flame and pressure risk area
Maintenance access / filter change
4. Mounting
Legs
Cleaning valve
Relief Panel Sensor
Bag / container
5. Duct system
Dimensioning / transport velocity
Pressure resistant inlet (Yes)
Isolation valve (Yes)
Suction source
6. Electrical Installation
Control voltage
Connections – Connection box
GND1 connected
Lightning conductor
Service switch ("NS-switch", accessory used y/n)
7. Compressed air
Air lines cleaned
Air pressure (6-10 bar)
36
FlexFilter EX
Date:
Preformed by:
Result