Review the entire hardware manual prior to Installation. Failure to follow these instructions may result
in serious personal injury, death and/or equipment damage
The information provided on this sheet is for Installation reference only. Please refer to the ACS880
Installation Manual for additional installation details
Mains/Power Wiring
L1
L2
PE
2
1a
1b
L1
L2
(PE)
PE
(PE)
**Disconnect / fusing provided by ITT on extended enclosure ACS880-07
1) Use a separate grounding PE cable (1a) or a cable with a seperate PE conductor (1b) if the
conductivity of the shield does not meet the requirements for the PE conductor.
2) 360-degree grounding is recommended if shielded cable is used. Ground the other end of
the input cable shield or PE conductor at the distribution board.
3) 360-degree grounding is required.
4) Line contactor (option +F250)
5) Common mode lter (option +E208)
6) du/dt lter or sine lter (options +E205 and +E206)
7) Use a separate grounding cable if the shield does not meet the requirements of IEC 61439-1
and there is no symmetically constructed grounding conductor in the cable.
8) Terminals of frame R9 cabinet:
UDC+
R-
UDC-
R+
9) Drive module
10) Fast acting fuses are required to protect drive. Fuse operating times should be less than 0.1
sec.
UL-Standard T/L type fuses
IEC-Standard gG or aR type fuses
Refer to Technical Data Section for details
Installation checklist
Check that...
1. The ambient operating conditions meet the speci cation in chapter Technical data.
2. The drive cabinet has been xed to oor, and if necessary due to vibration etc, also from
top to the wall or roof.
3. The cooling air will ow freely in and out of the drive cabinet.
4. If the drive will be connected to an IT (ungrounded) or a corner grounded TN network: The
optional EMC lter (+E200, +E202) of the drive (if any) has been disconnected.
5. If the drive has been stored over one year: The electrolytic DC capacitors in the DC link of
the drive have been reformed. See Converter module capacitor reforming instructions
(3BFE64059629 [English])
6. There is an adequately sized protective earth (ground) conductor between the drive and the
switchboard and the conductor has been connected to appropriate terminal. Proper grounding
has been measured according to the regulations.
7. There is an adequately sized protective earth (ground) conductor between the motor
and the drive and the conductor has been connected to appropriate terminal. Proper grounding
has been measured according to the regulations.
8. Only for drives with option +D150: There is an adequately sized protective earth (ground)
conductor between the user-installed brake resistor and the drive and the conductor has been
connected to appropriate terminal. Proper grounding has been measured according to the
regulations.
9. The supply voltage matches the nominal input voltage of the drive. Check the type
designation label.
10. The voltage setting of the auxiliary voltage transformer (T21) is correct.
11. The input power cable has been connected to appropriate terminals, the phase order is
right, and the terminal have been tightened (pull conductors to check).
12. The motor cable has been connected to appropriate terminals, the phase order is right,
and the terminals have been tightened (pull conductors to check).
13. The motor cable (and the resistor cable, if present) has been routed away from other
cables)
14. No power factor compensation capacitors have been connected to the motor cable.
15. If a drive bypass connection will be used : The direct-on-line contactor of the motor and
the drive output contactor are either mechanically or electrically interlocked (cannot be closed
simultaneously).
16. The external brake resistor (if present) has been connected to the appropriate terminals,
and the terminals have been tightened (pull the conductors to check.)
17. The brake resistor cable has been routed away from other cables.
18. The control cables have been connected to the appropriate terminals, and the terminals
have been tightened (pull the conductors to check.)
19. There are no tools, foreign objects or dust from drilling inside the drive.
20. All shrouds and cover of the motor connection box are in place. Cabinet doors have been
closed.
21. The motor and the driven equipment are ready for start.
WARNING
10
L1/
L2/
L3/
U1
V1
W1
~
~
4
UDC+
T1/
T2/
T3/
R-
UDC-
R+
U2
V2
W2
UDC-
UDC+
R-
R+
L3
U2
V2
W2
3
V1
U1
W1
L3
3~M
Drive type
U
= 400V
N
ACS880-07-0105A-3
ACS880-07-0145A-3
ACS880-07-0169A-3
ACS880-07-0206A-3
ACS880-07-0246A-3
ACS880-07-0293A-3
ACS880-07-0363A-3
ACS880-07-0430A-3
ACS880-07-0505A-3
ACS880-07-0585A-3
5
ACS880-07-0650A-3
ACS880-07-0725A-3
6
ACS880-07-0820A-3
ACS880-07-0880A-3
U
= 500V
N
ACS880-07-0096A-5
ACS880-07-0124A-5
ACS880-07-0156A-5
ACS880-07-0180A-5
ACS880-07-0240A-5
ACS880-07-0260A-5
ACS880-07-0302A-5
ACS880-07-0361A-5
ACS880-07-0414A-5
ACS880-07-0460A-5
ACS880-07-0503A-5
ACS880-07-0583A-5
ACS880-07-0635A-5
ACS880-07-0715A-5
ACS880-07-0820A-5
U
= 690V
N
ACS880-07-0061A-7
ACS880-07-0084A-7
ACS880-07-0098A-7
ACS880-07-0119A-7
ACS880-07-0142A-7
ACS880-07-0174A-7
ACS880-07-0210A-7
ACS880-07-0271A-7
ACS880-07-0330A-7
ACS880-07-0370A-7
ACS880-07-0425A-7
ACS880-07-0470A-7
ACS880-07-0522A-7
ACS880-07-0590A-7
ACS880-07-0650A-7
1. The cable sizing is based on max. 9 cables laid on a cable ladder side by
side, three ladder type trays one on top of the other, ambient temperature
30ĀC, PVC insulation, surface temperature 70ĀC (EN 60204-1 and IEC
60364-5-52/2001). For other conditions, size the cables according to local
saftey regulations, appropriate input voltage and the load current of the drive.
2. The cable sizing is based on NEC Table 310-16 for copper wires, 75ĀC
(167ĀF) wire insulation ar 40ĀC (104ĀF) ambient temperature. Not more than
three current-carryoing conductors in raceway or cable or earth (directly
buried). For other conditions, size the cable according to local saftey
regulations, appropriate input voltage and the load current of the drive.
PS220 Installation Quick Reference Floor Mount Units
Typical power cable sizes
1)
IEC
Frame
Cu cable type
AI cable type
size
2
2
mm
mm
R6
3x50
3x70
R6
3x95
3x120
R7
3x120
3x150
R7
3x150
3x240
2 x (3x70)
2 x (3x95)
R8
R8
2 x (3x95)
2 x (3x120)
2 x (3x120)
2 x (3x185)
R9
2 x (3x150)
2 x (3x240)
R9
R10
3 x (3x95)
3 x (3x150)
R10
3 x (3x120)
3 x (3x185)
3 x (3x150)
3 x (3x240)
R10
R11
3 x (3x185)
4 x (3x185)
R11
3 x (3x240)
4 x (3x240)
R11
3 x (3x240)
4 x (3x240)
R6
3x50
3x70
R6
3x95
3x95
R7
3x120
3x150
R7
3x150
3x185
R8
2 x (3x70)
2 x (3x95)
2 x (3x70)
2 x (3x95)
R8
R9
2 x (3x120)
2 x (3x185)
2 x (3x120)
2 x (3x185)
R9
R9
2 x (3x150)
2 x (3x240)
3 x (3x95)
3 x (3x150)
R10
R10
3 x (3x95)
3 x (3x150)
3 x (3x120)
3 x (3x185)
R10
R10
3 x (3x150)
3 x (3x240)
4 x (3x185)
4 x (3x185)
R11
R11
4 x (3x240)
4 x (3x240)
R6
3x25
3x35
R6
3x35
3x50
R7
3x50
3x70
R7
3x70
3x95
3)
R8
3x95
3x120
3)
R8
3x120
2 x (3x70)
R9
3x185
2 x (3x95)
R9
3x240
2 x (3x120)
R10
2 x (3x120)
3 x (3x120)
R10
2 x (3x120)
3 x (3x120)
R11
3 x (3x95)
3 x (3x120)
R11
3 x (3x95)
3 x (3x150)
3 x (3x120)
3 x (3x185)
R11
R11
3 x (3x150)
3 x (3x185)
3 x (3x150)
3 x (3x240)
R11
Drawing is not to scale
Drawn: HCLT 5-11-16
Dimensions in inches
[mm]
Checked: Brad 5-24-16
2)
US
Cu cable type
AWG/kcmil per phase
1
2/0
3/0
250 MCM
300 MCM
2 x 3/0
2 x 4/0
2 x 250 MCM
2x500 MCM or 3x250 MCM
2x600 MCM or 3x300 MCM
2x700 MCM or 3x350 MCM
3x500 MCM or 4x300 MCM
3x600 MCM or 4x400 MCM
3x600 MCM or 4x400 MCM
1
2/0
3/0
250 MCM
300 MCM
2 x 2/0
2 x 250 MCM
2 x 250 MCM
2 x 250 MCM
2x400 MCM or 3x4/0
2x500 MCM or 3x250 MCM
2x600 MCM or 3x300 MCM
2x700 MCM or 3x350 MCM
3x500 MCM or 4x300 MCM
3x600 MCM or 4x400 MCM
4
3
2
1/0
2/0
4/0
300 MCM
400 MCM
2x250 MCM or 3x2/0
2x300 MCM or 3x3/0
2x350 MCM or 3x4/0
2x400 MCM or 3x4/0
2x500 MCM or 3x250 MCM
2x600 MCM or 3x300 MCM
2x700 MCM or 3x350 MCM
SHEET
REV
Issue
B04934A
1 OF 1
0
-
PS220 214