Display control

18.2. Display

The following figure shows the main screen of the inverter and the meaning of each field.
a.
Current time, hh:mm.
b.
Current date, dd/mm/yy.
c.
Storage system data. The voltage in volts,
current in amps and state of charge are
displayed alternately. If COM is shown in place
of these values, there is no communication
with the BMS for the Li-Ion battery.
d.
PV array data. The voltage in volts and current
in amps of the PV array is shown alternately.
If the PV array is not available but the inverter
has started, the voltage of the DC bus is
displayed in volts.
e.
Percentage of nominal power and reason for
power reduction, if present
In the event that the inverter is connected to a grid or auxiliary generator and there is a power reduction,
(1)
the current power percentage and the most restrictive reason for the limitation are shown. If there is not power
limitation this percentage will not display. The different reasons for a power limitation are explained below,
indicated both with the letter viewed on the display and the code set by communications.
Letter viewed on the
Code sent by
display
communications
B
C
D
F
G
H
L
M
N
ABH2013IQM01_C - Installation and Operation Manual
a
10:23 AM
10:23 AM
c
d
(1)
Reasons for the power limitation
9
Batteries. Limitation due to the storage system state of charge or configuration.
Limitation caused by a setting sent through communications o by the self
1
consumption mode managed by the INGECON SUN EMS Board.
Power available Battery charge limitation from the grid/genset due to the power
available. This power is calculated with the rated power in the case of the
10
generator, or the contracted power in the case of the grid, minus the power
Grid frequency. Limitation due to the grid frequency variation. Applicable
4
Initial connection ramp. Limitation after a grid reconnection. Applicable
5
12
DC bus. Limitation due to high voltage in the internal DC bus.
Grid voltage drops. Limitation due to voltage drops in the grid. Applicable
13
Configuration. Battery charge limitation from the grid/genset, defined by a user
6
Grid consumption. Limitation due to the power consumption from the grid, when
15
working without batteries (only PV array) or when the batteries cannot absorb
b
09/07/17
09/07/17
e
f
g
h
f.
Consumption grid output data. The power
in Watts and the voltage in volts is shown
alternately.
g.
Auxiliary grid/genset input data. The power in
Watts and the voltage in volts of the auxiliary
grid/genset is shown alternately.
h.
This indicates that the system is operating
under the communication setting in grid
support mode. If the symbol flashes, this
means that communications with the
INGECON SUN EMS Board have been lost. As
a result, the display will switch to standby.
Description
consumed by the charges.
according to selected regulations.
according to selected regulations.
according to selected regulations.
setting.
energy.
Ingeteam
EN
ES
FR
PT
57