Display control
CAUTION
For photovoltaic self consumption installations with storage managed by the INGECON SUN EMS Board in
accordance with RD900/2015, this parameter must be set to 0W.
For more information about this type of installation, see the "Technical guide for installations with
INGECON SUN STORAGE 1Play" available on the Ingeteam website.

18.15. Configuring the digital outputs

These inverters have several voltage-free outputs which can have the following functionalities:
Options
NO CONFIGURATION
GENERATOR ON/OFF
LOW BAT. VOLTAGE
HIGH BAT. VOLTAGE
NEUTRAL GROUND
ON/OFF BY COM.
CONNECTED TO GRID
To configure the digital outputs, open MAIN MENU > CONFIGURATION > DIGITAL I/O.

18.16. Configuring the digital inputs

These inverters have several digital inputs which can have the following functionalities:
Options
NO CONFIGURATION
INVERTER START/STOP
CONNECT TO GRID
DRM0 COMMAND
To configure the digital outputs, open MAIN MENU > CONFIGURATION > DIGITAL I/O.

18.17. Configuring the Modbus ID

The Modbus ID is the inverter's identification number within the communications bus.
To configure the Modbus number, open MAIN MENU > CONFIGURATION > CHANGE MODBUS NODE.
ABH2013IQM01_C - Installation and Operation Manual
Description
No task assigned (default option)
Auxiliary generator activation signal
Signal used to indicate that the battery voltage is
lower than the minimum voltage configured. After
selecting this option the minimum voltage must be
set.
Signal used to indicate that the battery voltage is
higher than the maximum voltage configured. After
selecting this option the maximum voltage must
be set.
Neutral grounding of the consumers using a
normally open external contactor. In the event of
a TT (Off-grid) grid outage, the contactor will be
activated.
Digital output control via communications.
Signal to indicate that the inverter is connected to
the auxiliary grid or generator.
Description
No task assigned (default option)
Starts or stops the inverter
To connect the inverter to the auxiliary grid or
generator.
This functionality should only be configured for
using with the external DRED device, required by
Standard AS4777 (Australia).
If it is configured without the connection of the
external DRED device, the inverter will remain
stopped.
State of the normally open (NO) voltage-
free contact
OPEN
Turn off the generator: OPEN
Turn on the generator: CLOSED
Voltage above the limit: OPEN
Voltage below the limit: CLOSED
Voltage above the limit: OPEN
Voltage below the limit: CLOSED
TT neutral to ground in On-grid: OPEN
TT neutral to ground in Off-grid: CLOSED
Off: OPEN
On: CLOSED
Disconnected: OPEN
Connected: CLOSED
State of the voltage-free contactor /
Voltage level
OPEN / High level
Start: OPEN / High level
Stop: CLOSED / Low level
Do not connect: OPEN / High level
Connect: CLOSED / Low level
According to DRED external device policy.