Unit description
Insulation class
Markings
EMC and safety regulations
Distribution grid connection regulations
(1)
The maximum power of the inverter is a calculation of the battery voltage multiplied by the maximum discharge current (50 A).
compatible Li-Ion batteries.
In On-grid mode V
(3)
configured for the consumption grid).
be available if the battery voltage multiplied by the maximum discharge current reaches said value.
2.7. Description of cable inlets
C
A
F
B
Cable gland size
M16
M20
M25
ABH2013IQM01_C - Installation and Operation Manual
= 1.44 x V
(distribution grid voltage). In Off-grid mode V
MPPmin
AC
(4)
Never exceed this value. Consider the voltage increase of the panels 'Voc' at low temperatures.
D
E
I
G
H
3TL
Class I
CE
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-
6-4, EN 61000-3-11, EN 61000-3-12, EN 62109-1, EN
62109-2, EN 50178, IEC62103, AS62040.1, FCC Part 15
DIN V VDE V 0126-1-1, EN 50438, CEI 0-21, VDE-AR-N
4105:2011-08, G59/3, G83/2, AS4777.2:2015,
IEC 62116, IEC 61727, UNE 206007-1:2013, UNE
206006:2011, UNE 217001 IN:2015,NRS097-2-1, ABNT
NBR 16149, ABNT NBR 16150, DEWA, South African
Grid code, IEEE 929 Thailand MEA & PEA requirements,
Netbilling Chile
MPPmin
This parameter can be set on the display.
(6)
A.
Storage system. M20 cable gland
B.
PV array (in hardware type B there
is one photovoltaic inlet instead of
two). PV MC4 quick connectors
C.
Wi-Fi antenna or Ethernet cabling.
M20 cable gland
D.
CAN communication for Li-Ion
batteries with BMS. M16 cable
gland
E.
Installation of Wi-Fi reset button.
J
M16 cable gland
F.
PT-100 temperature sensor for
Lead-Acid batteries. M16 cable
gland
G.
Digital inputs. M16 cable gland
H.
Digital outputs. M16 cable gland
I.
Consumption grid. M25 cable gland
J.
Auxiliary grid/genset. M25 cable
gland
Admitted diameter range
4.5 mm ~ 10 mm
7 mm ~ 13 mm
9 mm ~ 17 mm
Ingeteam
6TL
(2)
See the list of
= 1.44 x V
(rated voltage
AC
(5)
This power will
15
EN
ES
FR
PT