Ingeteam
2.6. Specification table
Nominal power (up to 40 ºC)
Max. temperature for rated power
Maximum output fault current
Maximum output overcurrent protection
Storage system input (DC)
Voltage range with photovoltaic installed
Voltage range without photovoltaic installed
Maximum charge/discharge current
Battery type
Communication with Li-Ion batteries
PV array input (DC)
PV array maximum power
MPP Voltage range
(3)
Maximum input voltage
Maximum input current
Maximum short circuit current
Maximum inverter backfeed current to the array
MPPT
Number of strings
Auxiliary grid/genset input (AC)
Rated voltage
Voltage range
Nominal frequency
Frequency range
Maximum power
Maximum current
Cosine of Phi
Consumption grid output (AC)
Stand-alone mode
Power (25 ºC) 30 min, 2 min, 3s
Maximum current
Rated voltage
(6)
Nominal frequency
(6)
Cosine of Phi
On-grid mode
Maximum current
Voltage range
Frequency range
Cosine of Phi
Response time of the Back-up function
Performance
Maximum efficiency
Euroefficiency
General data
Cooling system
Air flow
Weight
Dimensions (height x width x depth)
Stand-by consumption
Operating temperature
Relative humidity (without condensation)
Protection class
Pollution degree
Maximum altitude
Overvoltage category
14
(1)
(1)
(4)
(5)
3TL
3 kVA
40 ºC
< 26 A rms (60 ms)
< 40 A rms (60 ms)
26 A rms
40 ~ 300 V
40 ~ 450 V
50 A
Lead-Acid, Li-Ion
CAN Bus 2.0
7.5 kWp
330
~ 480 V
(3)
550 V
20 A
22 A
0 A rms
1
2
230 V
172 ~ 264 V
50 / 60 Hz
40 ~ 70 Hz
11,500 VA
50 A rms
0 ~ 1
3,500 / 3,900 / 5,080 W
6,400 / 6,900 / 7,900 W
13 A rms
220 ~ 240 V
50 / 60 Hz
-0.8 ~ 1 ~ 0.8
50 A rms
172 ~ 264 V
40 ~ 70 Hz
-0.8 ~ 1 ~ 0.8
12 ms
95.5 %
95.1 %
Forced ventilation
27 m
/h
3
24.4 kg
470 x 360 x 180 mm
< 10 W
–20 ~ +65 ºC
4 ~ 100 %
IP65
2
2,000 m
Category III (AC) / Category II (DC)
ABH2013IQM01_C- Installation and Operation Manual
Unit description
6TL
6 kVA
40 A rms
(2)
11.5 kWp
30 A
33 A
26 A rms
96 %
95.2 %
45 m
/h
3
26 kg