Aventics DDL Serie, CL03 Serie Instrucciones De Servicio página 78

Ocultar thumbs Ver también para DDL Serie, CL03 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 181
78
AVENTICS | DDL, CL03/CL03-XL | R402003658–BDL–001–AE
Commissioning and Operation
S6
ON
OFF
Recognizing a short
circuit or open load
Byte Z is the start address of the diagnosis area for this DDL
participant in the controller.
The diagnostic messages for the various voltages can be
enabled via the S6 DIP switch. The LED display is always active.
The message to the superior system can be switched off.
Table 19:
Enabling the diagnostic messages
S6
Function
Bit
1
Data rate, see page 69
2
Switching the voltage tolerance for U BYTE 1-4 +10%
3
Data length, see page 71
4
Data length, see page 71
5
Transfer diagnostic message to superior
system. U BYTE 1
6
Transfer diagnostic message to superior
system. U BYTE 2
7
Transfer diagnostic message to superior
system. U BYTE 3
8
Transfer diagnostic message to superior
system. U BYTE 4
1)
No messages are transmitted in the default setting
(bits 2, 5, 6, 7, 8 with OFF = no/+15%)
The bus coupler can recognize if there is a short circuit or open
load in a valve solenoid. The diagnostic data is the same in both
cases. A short circuit may occur if e.g. the isolation of the valve
solenoid has been damaged. An open load may occur if e.g. the
valve solenoid in a valve has blown or if a contact has been
interrupted.
A short circuit can only be recognized if the valve output is
controlled.
An off valve output can only be recognized if it is not
controlled.
O
Exchange the defective valve if the diagnostic data reports a
short circuit or open load.
1)
ON
OFF
+15%
Yes
No
Yes
No
Yes
No
Yes
No

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cl03-xl serie

Tabla de contenido