IMPORTANT (NOTICE)
When using a device with an explosion-proof design, comply with the explosion protection
regulations. For Sensyflow FMT500-IG values, refer to the relevant certificates (ATEX, FM).
Before connecting the power supply, check that the set operating voltage matches the line
voltage.
Before making any other connections, you must first establish a connection between the
protective-conductor terminal and a protective conductor.
A line switch with adequate switching capacity and capable of fully isolating the device from
the supply system (all poles) must be installed within reach of the installation location. The
protective benefits of the protective conductor must not be canceled out as a result of this.
The protective conductor must not be interrupted or detached either inside or outside the
device.
In the case of 24 V UC supply power, the device may only be supplied with a safely isolated
low voltage (DIN VDE 0106).
Under no circumstances must the line voltage (115 V AC or 230 V AC) be connected to the 24
V UC input. Doing so would damage the device electronics beyond repair.
The maximum rated current for the overcurrent protection device on the installation side is
16 A.
6.3

Switching on

WARNING
Before switching the device on, check that all the tasks described in the previous sections
have been carried out correctly.
Failure to observe the information provided can result in severe injuries or death.
Check again to ensure that the set operating voltage matches the supply power voltage.
WARNING
Switching the device on while the rear housing cover is open can result in an electric shock; in
potentially explosive atmospheres, there is an additional risk of explosion.
This can result in severe injuries or death.
Only switch on the supply power when the housing cover is closed.
Switching on the supply power
The system will boot automatically and the device will be initialized. The device will then switch
to the set display screen and enter measuring mode.
IMPORTANT (NOTE)
If an error is detected during the system boot phase or during measurement, the problem will
be automatically highlighted on the display ("E" for error). The error can be read out in the
SERVICE MENU / STATUS MENU.
CI/FMT500-IG-X1
Sensyflow FMT500-IG
Commissioning