ABB Sensyflow FMT500-IG Manual De Instrucciones página 84

Ocultar thumbs Ver también para Sensyflow FMT500-IG:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 164
Electrical connections
Analog / HART module
11
Shield
12
+ I
analog output / HART
out
13
- I
analog output / HART
out
14
+ 24 V DC for external supply, 30 mA max.
15
GND 24 V
16
D
1
out
17
D
2
out
18
GND D
(D
out
out
19
D
1
in
20
D
2
in
21
GND D
(D
1 + 2)
in
in
22
Shield
PROFIBUS module
A
PROFIBUS DPV1 in / out signal
B
PROFIBUS DPV1 in / out signal
Note:
The system design is such that the entire bus connection will be
interrupted if you disconnect the PROFIBUS cable on the device. As
an alternative, please consider the version with DP M12 connection
socket (Section 5.1.2 ).
1)
Note regarding terminating resistor: The bus
termination with jumpers should only be used if just the device is
connected to this PROFIBUS line.
The incoming and outgoing PROFIBUS cables are connected to
terminals A (green cable) and B (red cable) respectively. The other
terminal blocks must not be used (CAN bus, for internal use only).
IMPORTANT (NOTE)
To help ensure safe operation of the module and to minimize EMC interference, the cable
shield for the PROFIBUS lines must be attached to the relevant terminals in the terminal box.
A low-resistance ground must also be connected to the grounding screw for the box (M6
threads) (cable cross section of at least 4 mm
IMPORTANT (NOTE)
Disconnecting the PROFIBUS cable on the device interrupts the entire bus connection.
Device versions that can be disconnected without causing an interruption: See Section 5.3.
30 - EN
84
1 + 2)
Cable shield
connected to
ground (PE)
by means of
capacitive
coupling
2
).
Sensyflow FMT500-IG
PROFIBUS
terminals A / B
Jumper for
PROFIBUS
terminating
resistor
1)
CI/FMT500-IG-X1

Publicidad

Tabla de contenido
loading

Tabla de contenido