Mounting
4.8
Installing the transmitter (with remote mount design)
With the remote mount design, cable lengths of up to 50 m (164 ft.) (ATEX Zone 0 / 1 / 21, FM
und Zone 2/22 versions with constant power method up to 25 m [82 ft.]) can be supported
between the sensor and the transmitter. The flowmeter sensor is installed in the pipe
component / weld-on adapter as described above. The transmitter is installed on a flat wall
surface, taking into account the maximum permissible ambient temperatures.
Fig. 17: Dimensions in mm (inch). Wall-mounted housing with remote mount design
The sensor and transmitter are connected by means of 10-pin, numbered terminal blocks, which
can be accessed once the covers have been removed from the wall-mounted housing and
sensor terminal box.
28 - EN
82
Cover in
connection area
Sensyflow FMT500-IG
CI/FMT500-IG-X1