10. HUMIDIFIER CONTROL VIA NETWORK
The variables shown in the list are a set of all the internal variables. DO NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE TABLE, OTHERWISE
HUMIDIFIER OPERATION MAY BE AFFECTED.
The serial connection (M11) is configured by default with the following parameters:
- Address 1
- Baud rate 19200 bps
- Frame 8,N,2 (not modifiable)
NOTICE:
it is recommended to set on the supervisor (Main) the maximum waiting time for a response from humiSonic - after being queried by the supervisor - of
at least 500 ms.
10.1 Supervisor variable list
"A"
analogue variables* (Modbus®: REGISTERS)
CAREL
Modbus®
1
0
Param. d0: TH probe temperature reading
2
1
Param. d1: TH probe humidity reading
3
2
Param. d2: Probe reading
4
3
Param. d5: Instant production
9
8
Param. d8: Dew point
"I"
integer variables (Modbus®: REGISTERS)
CAREL
Modbus®
1
128
Level access password
7
134
Humidifier status
0: disabled/standby
1: autotest
2: initialisation
2
129
Firmware release
15
142
Alarms, see chap. ALARMS:
bit0:
Alarm E0
bit1:
Alarm Et
bit2:
Alarm EF
bit3:
Alarm Ed
20
147
Parameter A0: Operating mode
21
148
Parameter A2: Type of external probe
22
149
Parameter A3: Probe minimum
23
150
Parameter A4: Probe maximum
24
151
Parameter A5: Probe offset
25
152
Parameter A6: Fan off delay time
26
153
Parameter A7: Fan speed
27
154
Parameter A8: Maximum evaporation time for no production alarm
28
155
Parameter A9: Minimum evaporation time for no production alarm
29
156
Parameter b0: Operating options
30
157
Parameter b1: Time between two washing cycles
31
158
Parameter b2: Inactivity time for washing on next start
32
159
Parameter b3: Washing time (fill + drain)
33
160
Parameter b4: Start delay time
34
161
Parameter b5: Operating hours for CL alarm
35
162
Parameter b6: Operating hours for CL alarm
36
163
Parameter b7: Piezoelectric transducer On/Off control range
37
164
Parameter b8: Probe disconnected delay
38
165
Parameter b9 TAM OFF delay
39
166
Parameter bA: Maximum fill time
40
167
Parameter bb: Refill time in evaporation
41
168
Parameter bC: Maximum drain time
42
169
Parameter bd: Drain opening time to completely empty tank
43
170
Parameter bE: Delay time after measuring low level for refilling
44
171
Parameter C0: Default display (terminal)
45
172
Parameter C1: Parameter A0: Baud rate
46
173
Parameter C2: tLAN address (if 0 Main controller)
47
174
Parameter C3: Serial address
48
175
Parameter P0: Maximum flow-rate
49
176
Parameter P1: Proportional control hysteresis
50
177
Parameter P2: Low humidity alarm threshold
51
178
Parameter P3: High humidity alarm threshold
52
179
Parameter SP: Humidity / dew point set point
53
180
Parameter d3: Operating hour counter
54
181
Parameter d4: Unit hour counter (not resettable)
60
187
Request via serial (if digital 37 set)
62
189
Identification of variable on Secondary unit to read/write from supervisor (see paragraph "Supervisor control")
63
190
Value of variable on Secondary unit identified by integer 62 (see paragraph "Supervisor control")
65
192
Parameter C4: Timeout for Main serial offline
69
196
AA: Waiting time for retry
70
197
Ab: Percentage of A8 for carrying out level test
71
198
Pn: Minimum production
72
199
bF: Drain activation delay in standby
73
200
AC: Maximum time to measure level when refilling
74
201
Ad: Maximum time to measure high level
82
209
AE: Restart fan time in standby for built-in probe reading
87
214
Secondary 1 firmware release
3: fill
4: production
5: drain
bit4:
Alarm EP
bit8:
bit5:
Alarm PU
bit9:
bit6:
Alarm H ¯
bit10: Alarm ES1
bit7:
Alarm H_
bit11: Alarm ES2
23
6: alarm reset
7: wash
8: cleaning procedure
Alarm EE
bit12: Alarm ES3
Alarm CL
bit13: Alarm OFL
bit14: Alarm EL
bit15: Alarm EtL
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
ENG
R/W
R
R
R
R
R
R/W
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R