CONTROLLING THE BOARD VIA NETWORK

The variables shown in the list are only some of the total variables available.
DO NOT CONFIGURE VA-RIABLES THAT ARE NOT SHOWN IN THE TABLE,
OTHERWISE THE OPERATION OF THE HUMIDIFIER MAY BE AFFECTED. NOTE:
The software release is made up of 4 digits and is shown on the sticker on
the back of the controller. For example, the code "1.080" indicates: hardware
release "1.0" and software release "8.0". Make sure the correct network address
has been set for parameter C3 (internal variable I13) before setting the
address of the CPY controllers. Each humidifi er is confi gured by default with
address 1, two units cannot have the same address.
"A"
analogue variables* (Modbus®: REGISTERS)
CAREL - Modbus®
3
param. d9: rated capacity in kg/h (see the table of parameters)
4
param. d7: maximum production in kg/h (see the table of parameters)
15
param. d3: instant steam fl ow-rate in kg/h; read-only. Format "#### = #### (100 = 100 kg/h)".
30
param. d6: current (A); read-only. Format "#### = #### (16 = 16a)".
33
param. C8:
maximum time with no data (sent to controller) over RS485 to generate stop production + "SU" alarm (see parameters table)
* The data from the controller should be interpreted with a decimal point.
E.g.: var. 3=150 means 15.0 kg/h
"I"
integer variables (Modbus®: REGISTERS)
CAREL
Modbus®
1
256
param. P0: maximum production (see the table of parameters)
2
257
param. A0: operating mode (see the table of parameters)
3
258
param. A1: unit of measure (see the table of parameters)
4
259
param. A2: type of production request (see the table of parameters)
5
260
param. b1: additional functions (see the table of parameters)
6
261
param. b2: off delay time (see the table of parameters)
7
262
param. b4: water conductivity (see the table of parameters)
8
263
param. b5: conductivity pre-alarm threshold (see the table of parameters)
9
264
param. b6: conductivity alarm threshold (see the table of parameters)
10
265
param. b7: foam control threshold (see the table of parameters)
11
266
param. b8: conductivity control inside the cylinder in steady operation compared to rated value
12
267
param. C0: rated value displayed (see the table of parameters)
13
268
param. C3: serial port address (see the table of parameters)
14
269
param. C4: baud rate (see the table of parameters)
15
270
param. C5: supervisor: frame (see the table of parameters)
16
271
param. C6: serial response transmission delay (see the table of parameters)
17
272
param. b9: reduce duration of drain to dilute cycle (see the table of parameters)
18
273
param. bb: cylinder maintenance limit time in hours (see the table of parameters)
19
274
param. bE: time limit between two periodical drain cycles (see the table of parameters)
20
275
param. bF: days delay for drain due to inactivity (see the table of parameters)
44
299
param. d1: external control signal
see paragraph "controlling production using variables I62 and I63, read-only; example format " #### = #### (0%-100%, step 1%)"
46
301
humidifi er status (read-only)0 = not active (no request, shutdown or disabled); 1 = start evaporation cycle; 2 = water fi ll in progress;
3 = evaporation in progress ; 4 = AFS drain ; 5 = water drain (to dilute or manual); 6 = end of water drain; 7 = complete drain for long
inactivity; 8 = complete drain from manual or network control; 9 = no water management; 10 = pre-wash; 11 = periodical drain
47
302
type of humidifi cation stage (read-only) 0 = not active; 1 = soft start; 2 = start of steady production the reduced production;
3 = steady production; 4 = reduced production; 5, 6, 7 = soft start
49
304
param. d5: conductivity of supply water [μS/cm] read-only, see the table of parameters
54
309
param. db: unit hour counter (not resettable, see the table of parameters)
55
310
param. dA: cylinder hour counter (resettable, see the table of parameters)
62
317
controls via RS485 ; bit 0: reset alarm log; bit 1: reset counter dA; bit 2: production request via variable I63; bit 3: pre-wash; bit 4: reset
active alarms. ; Bit 6: fl ag to enable
request most recent alarm; Bit 9: fl ag to load fi rst alarm in log; Bit 12: fl ag to enable create user backup. Except for bit2, the others are
always read as 0. On power-up, all the bits are equal to 0.
63
318
production request via network (when I62 bit2 = 4) (0%-100%, step 1%).
64
319
control board match-digit (read-only)
67
577
param. c7 (see the table of parameters)
83
338
alarm status: Bit 0: at least one BLOCK alarm present ; Bit 1:at least one DISAB alarm present; Bit 2: at least one WARN alarm present
84
339
alarms with shutdown (read-only) bit n=0 alarm not active, bit n=1 alarm active. See table of alarms: bit 0: alarm Mn; bit 1: alarm EC;
bit 2: alarm E1; bit 3: alarm E0; bit 4: alarm EH; bit 5: alarm EP; bit 6: not used; bit 7: not used.
85
340
alarms with disabling (read-only) bit n=0 alarm not active, bit n=1 alarm active. See table of alarms: bit 0: alarm EU (automatic reset);
bit 1: alarm E3; bit 2: alarm EF (automatic reset); bit 3: alarm Ed; bit 4: not used; bit 5: not used; bit 6: not used; bit 7: not used.
stop production + alarm for serial disconnected
39
; Bit 7: fl ag to request oldest alarm; Bit 8: fl ag to
"UE BASIC" +030220632 - rel. 2.3 - 20.01.2009
ENG
Tab. 11.g