operation of the photocell. The photocell does not "detect" daylight
or the light from a common lamp. Its sensitivity can be tested
using a flame (lighter, candle). To ensure a proper operation,
the cell voltage value must be sufficiently stable and not go
below the minimum value required for the specific equipment.
The check is performed between the terminals of the electric
panel as shown in the wiring diagram.
When the burner is working at its "minimum" output, adjust the air
and diesel in the proper quantities to ensure a good combustion.
After adjusting the air for the operation at the "minimum"
output, increase the power and proceed to define the
operating curve as described in the equipment manual. It
is recommended to check combustion using the specific
instrument at all intermediate points on the modulation curve.
The maximum output is obtained with a return pressure of
approx. 17 - 18 bar at a pump pressure of 25 bar (0002922840
стр. 15). It is recommended not to exceed the value of 13 %
of CO
in the smoke.
2
14 / 28
0006081557_201310