PROBLEM
ALARM SIGNAL
flashing
The barrier does
not open or close.
86
POSSIBLE CAUSE
Release device open.
Open barrier inspection hatch (if
the emergency stop micro-switch
is installed).
LOCKS connectors incorrectly
connected.
STOP button/contact active for
more than 5 s.
For MASTER-SLAVE systems, the
ACS/BA/60 BreakAway system is
active on the MASTER barrier.
Encoder 1 not connected.
Encoder 2 not connected.
Severe encoder 1 malfunction.
Severe encoder 2 malfunction.
(EnE5)
Encoder 1 malfunction.
Operation in battery mode.
Encoder 2 malfunction.
Operation in battery mode.
Encoder 1 calculation error.
Encoder 2 calculation error.
Inverter overheat protection trig-
gered.
(btLO)
Flat batteries.
No RS485 serial communication
between MASTER barrier and
SLAVE barrier.
Serial communication interfer-
ence: two MASTER controllers
detected.
Parameter configuration trans-
fer error between MASTER and
SLAVE.
Controller unit models not com-
patible.
(COM5)
Incompatibility between firmware
versions of controller units.
CORRECTIVE ACTION
AGILIK-KB-BI/004HP-BI/006-BI/008:
turning the key two complete turns clockwise.
BIONIK4: Close the release lock cover and turn the key.
Close the inspection hatch correctly and check the
micro-switch connection.
Check the connector connections.
Jumper one of the two LOCKS connectors.
Check connections to STOP button.
Check the BreakAway system and if the alarm event is
solved, re-engage the ACS/BA/60 system.
Check connection to encoder.
Replacing the encoder is recommended if the problem
persists.
Check connection to encoder.
Replacing the encoder is recommended if the problem
persists.
Press TEST button. If the error code is displayed again,
switch off the controller unit, wait 5 seconds and switch
on again. Replace the encoder if the problem persists.
Press TEST button. If the error code is displayed again,
switch off the controller unit, wait 5 seconds and switch
on again. Replace the encoder if the problem persists.
Press TEST button or perform 3 command requests
in succession. Replace the encoder if the problem
persists.
Batteries almost flat.
Press TEST button or perform 3 command requests
in succession. Replace the encoder if the problem
persists.
Batteries almost flat.
Repeat acquisition procedure.
Repeat acquisition procedure.
Function is restored automatically within 2 minutes.
Wait for mains power to be restored.
Check connection to terminals COM-LNA-LNB.
Check settings of parameter
.
Check that battery kit is installed on both MASTER and
SLAVE barriers.
Check settings of parameter
.
Check connection to terminals COM-LNA-LNB.
Check installation and replace one or both controller
units.
Check parameter
. Both controllers must have the
same firmware version.
Contact the technical assistance.