Safety input and command status (TEST mode)

With no currently active intentional commands, press the TEST button and check the following:
DISPLAY POSSIBLE CAUSE
MASTER barrier not moving. STOP con-
tact of MASTER barrier open
(rS)
(message visible for SLAVE barrier).
Detachable boom support system
enabled or not connected or incorrect
connection.
Safety STOP contact open.
Release device open.
Barrier inspection hatch open.
Sensing edge COS not connected or in-
correctly connected.
Photocell FT not connected or incorrectly
connected.
If occurs with no voluntary command, the
contact may be faulty or one of the but-
tons may be incorrectly connected.
If occurs with no command, the contact
may be faulty or the timer may be incor-
rectly connected.
N.B: press TEST to exit TEST mode.
We recommend troubleshooting safety device and input status errors with "corrective action by software" only.
84
ACTION BY SOFTWARE
-
Check the settings of parameter
-
-
-
Set the parameter
if not used or
to disable.
Set parameters
and
used or to disable.
-
-
-
-
-
PHYSICAL CORRECTIVE ACTION
Check STOP button/contact on MASTER
controller.
Install a STOP button (NC) or jumper the
ST contact with the COM contact of the
MASTER controller.
.
Check the correct system connection to
the control unit.
Check the STOP button/contact.
Install a STOP button (NC) or jumper the
ST contact with the COM contact.
AGILIK-KB-BI/004HP-BI/006-BI/008
Lock by turning the key two complete
turns clockwise.
Check that the microswitch contact is
connected correctly.
BIONIK4
Close the release lock cover and turn
the key.
Check that the microswitch contact is
connected correctly.
Close the barrier inspection hatch.
Check connection to microswitch.
If not used jumper contact COS with
contact COM.
If not used jumper contact FT with con-
if not
tact COM.
Check connection referring to relative
connection diagram (figures 4-5).
Check PP - COM contacts and connec-
tions to button.
Check CH - COM contacts and connec-
tions to buttons.
Check AP - COM contacts and connec-
tions to button.
Check PED - COM contacts and connec-
tions to button.
Check contacts ORO - COM.
Do not jumper this contact if not used.