7.2.2) Level one programming (ON-OFF functions)
Level 1 functions are all factory set to "OFF". However, they can be changed at any time as shown in Table 8. Follow the procedure carefully,
as there is a maximum time of 10 seconds between pressing one key and another. If a longer period of time lapses, the procedure will finish
automatically and memorize the modifications made up to that stage.
Table 8: changing ON-OFF functions
1.
Press and hold key [Set] (approx. 3 s)
2.
Release the [Set] key when L1 LED starts flashing
3.
Press keys [s] or [t] to move the flashing LED onto the LED representing the function to be changed
4.
Press the [Set] key to change the state of the function (short flashing = OFF; long flashing = ON)
5.
Wait 10 seconds before leaving the programme to allow the maximum time to lapse.
Note: Points 3 and 4 can be repeated during the same programming phases in order to set other functions to ON or OFF
7.2.3) Level two functions (adjustable parameters)
Table 9: programmable function list: level two
Input LED
Parameter
L1
Pause Time
L2
Step-by-step
Function
L3
Obstacle
detection
sensitivity
L4
Open gate
indicator
output
L5
Motor force
control
14
Led (level)
Value
L1
5 Seconds
L2
15 Seconds
L3
30 Seconds
L4
45 Seconds
L5
60 Seconds
L6
80 Seconds
L7
120 Seconds
L8
180 Seconds
L1
Open - stop - close - stop
L2
Open - stop - close - open
L3
Open - close - open - close
L4
Apartment block
L5
Apartment block (more than 2" generates stop)
L6
Step-by-step 2 (less than 2" generates partial open)
L7
Dead man
L8
Opening in semi-automatic mode, closing in
dead man mode
L1
Very high sensitivity (lightweight gates)
L2
Very high sensitivity
L3
High sensitivity
L4
Medium sensitivity
L5
Medium-low sensitivity
L6
Low sensitivity
L7
Very low sensitivity
L8
Very low sensitivity (heavyweight gates)
L1
Gate Open Indicator function
L2
Active if leaf closed
L3
Active if leaf open
L4
Active with radio output 2
L5
Active with radio output 3
L6
Active with radio output 4
L7
Maintenance indicator
L8
Electric lock
L1
Set at 40%
L2
Set at 50%
L3
Set at 60%
L4
Set at 80%
L5
Set at 100%
L6
Semiautomatic 1=40÷100% (1)
L7
Semiautomatic 2=60÷100% (1)
L8
Automatic = 0÷100% (2)
Example
SET
L1
o
SET
Description
Adjusts the pause time, i.e. the time which
lapses before automatic closure. This will
only have an effect if automatic closing is
active.
Manages the sequence of controls associ-
ated with the Step-by-Step input or to the
1st radio command.
Controls obstacle detection sensitivity. Take
care that sensitivity is also influenced by the
force of the motor (see L5); the motor force
should always be adjusted beforehand, to
enable correct settings of obstacle detec-
tion sensitivity.
Adjust the function associated with the
open gate indicator output (regardless of the
associated function, when active, it supplies
a voltage of 24V -30 +50% with maximum
power of 4W).
After start-up of the motor, set the force
to adapt it to the weight of the gate. The
control system also measures the ambient
temperature, increasing force automatically
in the event of particularly low temperatures.
3s
SET
10s