4.4.3

Hygienic versions

WARNING
Loss of sanitary approvals
Loss of sanitary approvals can result from improper installation/mounting.
Take special care when installing in hygienic or sanitary applications. Comply with installation/mounting guidelines to
ensure cleanliness and the ability to keep the wetted parts in a position to be readily cleanable. (See relevant
EHEDG/3A documentation - not supplied).
NOTICE
Loss of sanitary approvals
For 3-A Sanitary Approved device installation where the customer tank process connection exists, a leak detection port
of minimum 2.4 mm diameter must be provided at the lowest point in the process connection where leakage can occur.
If leakage is detected at any time while the device is installed, then the device process connection parts must be
disassembled and thoroughly cleaned prior to gasket replacement and reassembly.
Note
For Hygienic encapsulated antenna, the lens acts as a gasket/seal and should be used in conjunction with a cleanable
seal as required by the specific process connections (for example, DIN 11864-3).
Hygienic encapsulated antenna leak detection port
Orientation mark for leak detection port
Leak detection port
16
SITRANS LR250 (mA/HART)
A5E33469191-AA, 08/2014