Installation; Anti-Freeze Function; Connecting Up System - Sime MURELLE 25/55 OF ErP Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2 

INSTALLATION

The.boiler.must.be.installed.in.a.fixed.loca-
tion. and. only. by. specialized. and. qualified.
firms. in. compliance. with. all. instructions.
contained. in. this. manual.. Furthermore,.
the.installation.must.be.in.accordance.with.
current.standards.and.regulations..
2.1 
INSTALLATION
-. In.the.rooms.where."type B".boilers.are.
installed,. the. air. required. for. correct.
combustion.of.the.gas.consumed.by.the.
appliance. must. be. able. to. flow. in.. It. is.
therefore. necessary. to. make. openings.
that.cannot.be.blocked.in.the.outer.walls,.
which. must. be. at. least. 6. cm
kW. of. thermal. capacity. installed. and.
with,.in.any.case,.a.minimum.of.100.cm
-. Boilers. are. suitable. for. functioning. in. a.
partially.protected.place,.as.according.to.
EN. 15502,. with. maximum. environmen-
tal. temperature. of. 60°C. and. minimum.
of. -5°C.. We. recommend. installation. of.
these.boilers.under.the.protruding.slope.
of. a. roof,. on. a. balcony,. or. in. a. pro-
tected. niche,. always. providing. they. are.
not.directly.exposed.to.adverse.weather.
(rain,. hail,. snow).. The. boilers. are. . pro-
vided. already. equipped. with. anti-freeze.
functions.
-. In. existing. buildings,. this. natural. intake.
water.heater.must.only.be.connected.to.a.
hot-air.device.shared.by.different.homes.
to. expel. combustion. residues. from. the.
room.where.the.water.heater.is.installed..
The.water.heater.draws.air.required.for.
combustion. directly. from. the. room,. and.
is. equipped. with. a. wind-proof. chimney..
Due. to. poorer. efficiency,. any. other. use.
of. this. water. heater. is. to. be. avoided. as.
it. would. result. in. higher. power. con-
sumption.and.higher.operating.costs.(EU.
REGULATION.No..813/2013).
2.1.1 
Anti-freeze function
The. boilers. are. equipped. with. anti-freeze.
function.which.activates.the.pumps.and.the.
burner.when.the.temperature.of.the.water.
contained. inside. the. appliance. drops. to.
below.6°C..
The.anti-freeze.function.is.ensured,.howe-
ver,.only.if:
-. the.boiler..is.correctly.connected.to.the.. .
. gas.and.electricity.supply.circuits;
-. the.boiler.is.constantly.fed;
-. the.boiler.ignition.is.not.blocked;
-. the.essential.components.of.the..
. boiler.are.all.in.working.order
In. these. conditions. the. boiler. is. protected.
against. frost. down. to. an. environmental.
temperature.of.-5°C.
ATTENTION:  In  the  case  of  installation 
in  a  place  where  the  temperature  drops 
below  0°C,  the  connection  pipes  must  be 
protected. 
2
. for. every.
2
.
2.2 
BOILER SUPPORT BRACKET 
(fig. 4)
For.the.mounting.of.the.support.bracket.of.
the. boiler,. which. is. supplied,. observe. the.
following.instructions.(fig..4):
–. Fix. the. bracket. to. the. wall. with. appro-
priate.dowels.
–. Check. with. a. spirit. level. that. it. is. per-
fectly.in.horizontal.plane.
–..To.fix.the.boiler.with.the.lives.put.in.evi-
dence.in.figure.
2.2.1 
Complementary accessories
To. facilitate. connecting. the. boiler. to. the.
system,. the. following. accessories. can. be.
supplied.on.request:
–. Installation.plate.code.8081217
–. Curvette.kit.code.8075423
.
–. Taps.kit.code.8091833
–. Mixed.area.kit.ZONA.MIX.code.8092234.
For. detailed. information. on. the. assembly.
of. fittings,. see. the. instructions. contained.
in.the.box.
2.2.2 
Flow regulator (fig. 5)
In. entrance. of. the. D.H.W.. a. regolator. of.
color.capacity.is.installed.brown;.the.rego-
lator. is. inserted. in. a. bag. to. equipment. of.
the.boiler.
2.3 
CONNECTING UP SYSTEM
To.protect.the.heat.system.from.damaging.
corrosion,. incrustation. or. deposits,. before.
installation. it. is. extremely. important. to.
clean. the. system. using. suitable. products.
such. as,. for. example,. Sentinel  X300  (new 
systems), X400 and X800 (old systems) or 
Fernox  Cleaner  F3.. Complete. instructions.
are.provided.with.the.products.but,.for.fur-
ther. information,. you. may. directly. contact.
SENTINEL. PERFORMANCE. SOLUTIONS.
LTD.or.FERNOX.COOKSON.ELECTRONICS.
For. long-term. protection. agains. corrosion.
and.deposits,.the.use.of.inhibitors.such.as.
Sentinel  X100  or  Fernox  Protector  F1. is.
recommended. after. cleaning. the. system..
It. is. important. to. check. the. concentration.
of. the. inhibitor. after. each. system. modifi-
cation. and. during. maintenance. following.
the. manufacturer's. instructions. (specific.
tests. are. available. at. your. dealer).. The.
safety. valve. drain. must. be. connected. to. a.
collection. funnel. to. collect. any. discharge.
during. interventions.. If. the. heating. system.
is. on. a. higher. floor. than. the. boiler,. install.
ES
PT
ENG
Fig..4
Fig..5
69

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido