of a class conforming to the standard EN
607301 (clean electrical contact).
2.9.2
Climatic regulator CR 53
connection (optional)
The boiler is designed for connectio to a cli-
matic regulator, supplied on request (code
8092227), for the management of a hea-
ting circuit. The electronic card will conti-
nue to manage information visualisation,
the setting of the sanitary set and the hea-
ting of the second circuit, and the boiler
parameters by means of the keys on the
control panel. For installation and use of
the climatic regulator, follow the instruc-
tions included in the packaging.
NOTE: Reset parameter 10 to 2 (PAR 10
= 2).
2.9.3
Remote control CR 73
connection (optional)
The boiler is designed for connection to a
2.9.6
Use with different
electronic systems
Some examples are given below of boiler
systems combined with different electronic
systems. Where necessary, the parame-
ters to be set in the boiler are given. The
electrical connections to the boiler refer to
the wording on the diagrams (figg. 11-
11/a). The zone valve control starts at
every demand for heating of the zone 1 (it
is from part of the TA1 or the CR).
Description of the letters indicating the
components shown on the system dia-
grams from 1 to 14:
M
C.H. flow
R
C.H. return
CR
Remote control CR 73
SE
External temperature sensor
TA 1-2-3-4
Zone room thermostat
CT 1-2
Zone chronothermostat
VZ 1-2
Zone valve
RL 1-2-3-4 Zone relay
Sl
Hydraulic separator
P 1-2-3-4
Zone pump
SB
D.H.W. sensor
PB
D.H.W. pump
IP
Floor system
EXP
Expansion card ZONA MIX (code
8092234)/INSOL
(code 8092235)
VM
Three-way mixer valve
86
remote control unit, supplied on request
(code 8092226).
The remote control unit CR 73 allows for
complete remote control of the boiler,
except release of the boiler.
The boiler display will show the following
message:
For installation and use of the remote con-
trol, follow the instructions in the package.
NOTE: Ensure PAR 10 set to 1 (PAR 10 =
1).
2.9.4
External sensor connection
The boiler is designed for connection to an
external temperature sensor, supplied on
request (code 8094101), which can auto-
1
BASIC SYSTEM
SYSTEM WITH A DIRECT ZONE AND ROOM THERMOSTAT, OR WITH
A CLIMATIC REGULATOR CR 53 (Code 8092227) OR WITH REMOTE
CONTROL CR 73 (Code 8092226) AND EXTERNAL SENSOR (Code
8094101)
CR
SE
CR
SE
TA1
TA
matically regulate the temperature value of
the boiler output according to the external
temperature.
For installation, follow the instruction in the
package. It is possible to make corrections
to the values read by the drill acting on the
PAR 11.
2.9.5
D.H.W. sensor connection
in vers. "12-20-25-30-35 T"
The "12-20-25-30-35 T" version is provi-
ded with a D.H.W. sensor (SB) linked to the
connector CN5.
When the boiler is coupled to an external
boiling unit, introduce the sensor into the
special sleeve in the boiling unit.
ATTENTION: The "T" version is designed
for connection to a remote boiling unit,
for use ONLY FOR HEATING it is neces-
sary:
- to disconnect the D.H.W. sensor (SB);
- set PAR 2 and 4.
Operations must be carried out by autho-
rized and qualified technicians.
PARAMETERS SETTINGS
If using CR 53 set parameter
10 to 2 (PAR 10 = 2)