Switching Off - salmson SIL Serie Instalacion Y Puesta En Servicio

Ocultar thumbs Ver también para SIL Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8.1.1 Activation

8.1.2 Switching off

8.1.3 Operation
Installation and operating instructions SIL, DIL, PBS
• By briefly switching on, check whether the direction of rotation
agrees with the arrow on the fan cover. If the direction of rotation is
incorrect, proceed as follows:
• For direct starting: Swap 2 phases on the motor terminal board
(e.g. L1 for phase L2),
• For Y- start: Swap the winding start and winding end of 2 windings
on the motor terminal board (e.g. V1 for V2 and W1 for W2).
• The unit may only be switched on when the shut-off device on the
pressure side is closed! Only after full speed has been reached may the
shut-off device be slowly opened and be adjusted to the duty point.
The unit must run smoothly and free of vibration.
The mechanical seal ensures that a seal will not leak and requires no
special setting. Should there be a small leakage at the beginning, it
will stop when the initial inlet phase of the gasket is over.
• Immediately after the conclusion of all work, all the provided safety
and protection equipment items must be properly installed and put
into operation.
DANGER! Risk of fatal injury!
Failure to install safety devices on the terminal box or near the
coupling can cause electrical shock or contact with rotating parts,
potentially resulting in life-threatening injuries.
• Immediately after maintenance, all previously removed safety
devices, such as terminal box covers or coupling covers, must be
reinstalled!
• Close the shut-off device in the pressure pipe.
NOTE:
In case a non-return valve is installed in the pressure pipe, the shut-
off device can remain open insofar as a counter pressure is present.
CAUTION! Risk of property damage!
Risk of damage due to incorrect handling.
• When switching off the pump, the shut-off device in the inlet pipe
may not be closed.
• Switch off the motor and allow it to coast down completely. Ensure
the coasting is smooth.
• For longer downtimes, close the shut-off device in the inlet pipe.
• For longer periods of non-use and/or danger of freezing, drain the
pump and secure it against freezing.
• After removing the pump, keep it in a dry and dust-free storage.
NOTE:
The pump should always run smoothly and vibration-free and not be
operated in conditions other than those specified in the catalogue/
data sheet.
DANGER! Risk of fatal injury!
Failure to install safety devices on the terminal box or near the
coupling can cause electrical shock or contact with rotating parts,
potentially resulting in life-threatening injuries.
• Immediately after maintenance, all previously removed safety
devices, such as terminal box covers or coupling covers, must be
reinstalled!
DANGER! Risk of burns or freezing to the pump when body parts
come into contact with the pump!
Depending on the pump or system operating conditions (fluid tem-
perature), the entire pump can become very hot or very cold.
• Keep a safe distance during operation!
English
47

Publicidad

Tabla de contenido
loading

Tabla de contenido