Sime Murelle HE 12 T ErP Instrucciones Originales página 103

Ocultar thumbs Ver también para Murelle HE 12 T ErP:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

working. in. heating. mode. at. maximum.
power,.with.cut.off.at.80°C.and.re-ignition.
at. 70°C. (ATTENTION!  Temperature  may 
reach excessive values when using unpro-
tected  low  temperature  plants.  Before 
activating  the  chimney  sweep  function 
make  sure  that  the  radiator  valves  or 
eventual zone valves are open).
The. test. can. also. be. carried. out. with. the.
boiler.working.in.D.H.W..mode..
For.this,.after.activating.the.chimney.sweep.
function,.open.one.or.more.hot.water.fau-
cets.. Under. these. conditions,. the. boiler.
5
5
will. function. at. maximum. power. with. the.
D.H.W.. circuit. kept. at. between. 60°C. and.
50°C..During.the.test,.the.hot.water.faucets.
must.remain.open.
3
3
If. the.
key.
. and.
.
are. pressed. during.
the.15.minutes.of.the.chimney.sweep.fun-
1
1
ction,. the. boiler. will. be. brought. respecti-
vely.to.maximum.and.minimum.power.
5
The chimney sweep function will automa-
2
2
tically switch off after 15 minutes or when 
3
is pressed again.
the key .
.
4
4
1
4.5.2 
Cleaning the filter "Aqua Guard 
Filter System" (fig. 22)
2
To.clean.the.filter,.close.the.delivery/return.
on/off.taps,.turn.off.the.power.to.the.con-
trol. panel,. remove. the. casing. and. empty.
4
the.boiler.using.the.drain.provided..
Place.a.container.for.collection.underneath.
the.filter,.unscrew.the.cap.and.proceed.to.
clean. the. filter,. removing. impurities. and.
limestone.deposits..
Check.the.seal.o-ring.before.reassembling.
the.cap.with.the.filter.
4.5.3 
Operation floor drying
(fig. 22/a)
The. operation. floor. drying. keeps. the. floor.
at. a. pre-established. temperature. profile.
and. it. is. activated. only. for. those. systems.
combined. with. the. mixed. zone. card.
ZONA.MIX.code.8092234..The.temperature.
profiles. can. be. selected. by. means. of. the.
installer.parameter.PAR.43:.
0.=.Not.activated.function
1.=.Curve.setting.A
2.=.Curve.setting.B
3.=.Curve.setting.A.+.B
The. turning. off. of. . the. function. happens.
clicking. on. the. button. OFF. (return. of. PAR.
43. to. the. value. 0). or. automatically. at. the.
end.of.the.function..
The.set.of.the.mixed.zone.follows.the.deve-
lopment.of.the.selected.curve.and.reaches.
a. maximum. of. 55°C.. During. the. function.
all.the.other.heating.demands.are.ignored.
(heating,. sanitary,. antifreeze. and. chimney.
sweep)..
During. the. functioning. the. display. shows.
the. remaining. days. for. the. completion. of.
the.function.(example.mains.digits.-15.=.15.
days. lack. to. the. end. of. the.
diagram.fig..22/a.reports.the.development.
function)..
The.
ES
PT
ENG
Fig..21
Fig..22
103

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Murelle he 25 t erpMurelle he 30 t erpMurelle he 35 t erp

Tabla de contenido