External Sensor - Sime Murelle HE 12 T ErP Instrucciones Originales

Ocultar thumbs Ver también para Murelle HE 12 T ErP:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.4 
EXTERNAL SENSOR 
(fig. 13)
If. there. is. an. external. sensor,. the. heating.
settings.SET.can.be.taken.from.the.climatic.
curves.according.to.the.external.temperatu-
re.and,.in.any.case,.limited.to.with.the.range.
values. described. in. point. 3.3. (parameters.
PAR.25.for.zone.1.and.PAR.26.for.zone.2)..
The.climatic.curve.to.be.set.can.be.selected.
from. a. value. of. 3. and. 40. (at. step. 1)..
Increasing. the. steepness. of. the. curves. of.
fig..13.will.increase.the.output.temperature.
as.the.external.temperature.decreases.
3.5 
CARD FUNCTIONING
The. electronic.card. has. the. following. fun-
ctions:
–. Antifreeze.protection.of.the.heating.and.
sanitary.water.circuits.(ICE).
–. Ignition.and.flame.detection.system.
–. Control.panel.setting.for.the.power.and.
the.gas.for.boiler.functioning.
–. Anti-block.for.the.pump.which.is.fed.for.
a.few.seconds.after.24.hours.of.inactivi-
ty.
–. Antifreeze.protection.for.boilers.with.an.
accumulation.boiling.unit.
–. Chimney. sweep. function. which. can. be.
activated.from.the.control.panel.
–. Temperature. which. can. be. shifted. with.
the.external.sensor.connected..
. It.can.be.set.from.the.control.panel.and.
is.active.on.the.heating.systems.of.both.
circuit.1.and.circuit.2.
–. Management. of. two. independent. hea-
ting.circuit.systems.
–. Automatic. regulation. of. the. ignition.
power.and.maximum.heating...
. Adjustments. are. managed. automati-
cally. by. the. electronic. card. to. guaran-
tee. maximum. flexibility. in. use. of. the.
system.
–. Interface. with. the. following. electronic.
systems:. remote. control. SIME.HOME.
code. 8092280/81,. thermal. regulator.
RVS,. connected. to. a. management. card.
of.a.mixed.zone.ZONA.MIX.code.8092234.
and.card.solar.INSOL.code.8092235.. 
  NOTE: If using RVS set parameter 10 to 
3 (PAR 10 = 3). 
3.6 
TEMPERATURE 
DETECTION 
SENSOR
Table  4  shows. the. resistance. values. of. the.
heating,. DHW. and. exhaust. fumes. thermi-
stors..
If the heating sensor (SM) is faulty or open 
circuit, the boiler will not function on either 
heating or DHW (ALL 05).
If the exhaust fumes sensor (SF) is faulty or 
open circuit, the boiler will not function on 
either heating or DHW (ALL 14).
If  the  DHW  sensor  (SS)  is  faulty  or  open 
circuit, the boiler will work without modu-
ATTENTION:  curves  are  calculated  at  an  ambient  temperature 
of  20°C.  The  user  can  act  on  the  boiler  controls  to  change  the 
environment set  for which the bend has been calculated by ±5°C. 
lation to the DHW temperature.
TABLE 4 (SM - SS - SF sensors)
. Temperature.(°C).
Resistance.(Ω)
.
20.
12.090
.
30.
8.313
.
40.
5.828
.
50.
4.161
.
60.
3.021
.
70.
2.229
.
80.
1.669
3.7 
ELECTRONIC IGNITION
Ignition. and. flame. detection. is. controlled.
by.a.single.electrode.on.the.burner.which.
guarantees. reaction. in. the. case. of. acci-
dental.extinction.or.lack.of.gas.within.one.
second.
3.7.1 
Functioning cycle
Burner. ignition. occurs. within. max.. 10.
seconds.after.the.opening.of.the.gas.valve..
Ignition.failure.with.consequent.activation.
of.block.can.be.due.to:
–.
Lack of gas
  The. ignition. electrode. persists. in.
discharging. for. max.. 10. seconds.. If. the.
burner. does. not. ignite,. the. anomaly. is.
signalled.
. This.can.happen.the.first.time.the.boiler.
is. switched. on. after. a. long. period. of.
inactivity. due. to. the. presence. of. air. in.
the.gas.pipes
..
It.can.be.caused.by.a.closed.gas.tap.or.
by. a. broken. valve. coil. (the. interruption.
does.not.allow.for.opening)..
–. The electrode does not discharge.
. In.the.boiler,.only.the.opening.of.the.gas.
to.the.burner.can.be.detected..After.10.
seconds.the.anomaly.is.signalled..It.can.
be.caused.by.an.interruption.in.the.elec-
trode.wire.or.if.it.is.incorrectly.anchored.
to.the.connection.points..
. Or. the. electrode. may. be. earthed. or.
strongly. worn:. it. must. be. replaced.. Or.
the.electronic.card.may.be.defective.
–. No flame detected
.
After.start-up.the.electrode.continues.to.
discharge. even. when. the. burner. is. on..
After. 10. seconds,. the. discharge. stops,.
the.burner.is.switched.off.and.a.fault.is.
generated.
. This. fault. is. sometimes. caused. by. the.
shorting.of.the.electrode.cable.or.by.its.
improper.fixing.to.the.connection.points..
The.electrode.is.connected.to.the.earth.
or. badly. worn. and. must. be. replaced..
The.electronic.board.is.faulty.
In.the.case.of.a.sudden.lack.of.voltage,.the.
burner. will. immediately. switch. off.. When.
voltage. returns,. the. boiler. will. automati-
cally.start.up.again.
ES
PT
ENG
Fig..13
99