usable.height.of.the.water.trap.must.be.at.
least.150.mm.
2.7
FORCED EXHAUST
TYPE B23P - B53P
(fig. 9/a)
This. type. of. exhaust. pipe. is. installed. using.
the. special. kit,. code. 8089912/13.. For. kit.
assembly. instructions,. refer. to. point. 2.6..
Protect. the. intake. with. the. optional. acces-
sory,.code.8089501..
The.accessory.is.assembled.by.cutting.a.50.
mm. long. segment. from. an. ordinary. ø. 80.
extension. and. inserting. it. on. the. air. intake,.
on.which.the.accessory.is.then.fitted,.ancho-
red. to. the. pipe. segment. with. the. screws.
provided.(fig..9/a)...
Maximum flow resistance must be no more
than 10 mm H
O (version 12) - 15 mm H
2
(version 25-30-35) (ATTENTION: the total
length of each pipe should not exceed 25 m,
even if the total loss is below the maximum
applicable loss.)
As. the. maximum. pipe. length. is. determi-
ned. by. adding. up. the. flow. resistance. of.
the.various.individual.accessories.installed,.
refer.to.Table 1-1/a.for.calculation.
2.8
POSITIONING THE
OUTLET TERMINALS (fig. 10)
The. outlet. terminals. for. forced-draught.
TABLE 3
Siting.of.terminal.
. . .
A. -. below.openable.window.
B. -. below.ventilation.opening.
C. -. below.eaves.
D. -. below.balcony.(1).
E. -. from.adjacent.window.
F. -. from.adjacent.ventilation.opening.
G. -. from.horizontal.or.vertical.soil.or.drain.pipes.(2).
H. -. from.corner.of.building.
I. -. from.recess.in.building.
L. -. from.ground.level.or.other.treadable.surface.
M. -. between.two.terminals.set.vertically.
N. -. between.two.terminals.set.horizontally.
O. -. from.a.surface.facing.without.openings.or.terminals. 2000
P. -. as.above.but.with.openings.and.terminals.
1). Terminals. below. a. practicable. balcony. must. be. located. in.
such. a. way. that. the. total. path. of. the. smoke. from. its. outlet.
point.from.the.terminal.to.its.outlet.point.from.the.external.
perimeter. of. the. balcony,. including. the. height. of. possible.
railings,.is.not.less.than.2000.mm.
2). When.siting.terminals,.where.materials.that.may.be.subject.
to.the.action.of.the.combustion.products..are.present.in.the.
vicinity,.e.g.,.eaves,.gutters.and.downspouts.painted.or.made.
of.plastic.material,.projecting.timberwork,.etc.,.distances.of.
not. less. than. 1500. mm. must. be. adopted,. unless. adequate.
shielding.is.provided.to.guard.these.materials.
appliances. may. be. located. in. the. external.
perimeter.walls.of.the.building..
To.provide.some.indications.of.possible.solu-
O
2
tions,.Table 3.gives.the.minimum.distances.
to.be.observed,.with.reference.to.the.type.of.
building.shown.in.fig..10.
2.9
ELECTRICAL
CONNECTION
The.boiler.is.supplied.with.an.electric.cable..
Should.this.require.replacement,.it.must.be.
purchased.exclusively.from.SIME..
The.electric.power.supply.to.the.boiler.must.
be.230V.-.50Hz.single-phase.through.a.fused.
main. switch,. with. at. least. 3. mm. spacing.
Appliances.from.7.to.35.kW
(distances.in.mm)
600
600
300
300
400
600
300
300
300
2500
1500
1000
3000
cod. 8089501
between.contacts..
Respect.the.L.and.N.polarities.and.the.earth.
connection.
NOTE: SIME declines all responsibility for
injury or damage to persons, animals or
things, resulting from the failure to provide
for proper earthing of the appliance.
2.9.1
Chronothermostat connection
Connect. the. chronothermostat. as. indicated.
in.the.boiler.electrical.diagram.(see figs. 11
e
11/a)
after. having. removed. the. existing.
bridge..
The. chronothermostat. to. be. used. must. be.