ELECTRICAL AND GAS LEAK CHECKS
ELECTRICAL SAFETY CHECKS
After installation, confirm that all electrical wiring is installed in accordance with local and national regulations,
and according to the Installation Manual.
BEFORE TEST RUN - Check Grounding Work
Measure grounding resistance by visual detection and grounding resistance tester. Grounding resistance must
be less than 4.
DURING TEST RUN - Check for Electrical Leakage
During the Test Run, use an electroprobe and multimeter to perform a comprehensive electrical leakage test.
If electrical leakage is detected, turn off the unit immediately and call a licensed electrician to find and resolve
the cause of the leakage.
WARNING – RISK OF ELECTRIC SHOCK: ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL
CODES, AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN.
GAS LEAK CHECKS
There are two different methods to check for gas leaks.
Soap and Water Method - Using a soft brush, apply soapy water or liquid detergent to all pipe
connection points on the indoor unit and outdoor unit. The presence of bubbles indicates a leak.
Leak Detector Method - If using leak detector, refer to the device's operation manual for proper usage
instructions.
AFTER PERFORMING GAS LEAK CHECKS: After confirming that the all pipe connection points DO NOT leak,
replace the valve cover on the outside unit.