Installation of the control unit
3.1
Connection of the TENSION
26
23
24
25
Low Tension
+
-
input for transformer
BATTERY
The power supply line has to be protected from a magneto-termic switch or from a couple of 5A fuses.
A differential switch is useful if it is already available in the installation.
3.2
Connections of the MOTORS
Pay attention not invert the poles OPEN and CLOSE.
When the connection is finished, in case of doubts put manually the
gate in the middle and read Paragraph 4.2 to check the right direction
of the motors.
3.3

ANTENNA connections

In case of using a cable (as antenna) for the frequency
433.92mhz, you can cut at 17cm and connect it to the ter-
minal board 1.
1
2
3
3.5
Connection of the STOP device
Connection of the STOP control
Button: stop the control unit until a new contro.
Switch: it stops the automation until a new control.
3
4
5
6
7
30
27
28
29
8
9
10
The control unit can be powered 12 Vac/24 Vac
12 Vac:
Put the J12/24 as in the picture
230V input Primary
Set to "0" the set up S 21.
Transformer
24 Vac:
230Vac
Put the in J12/24 as shown
Set "1" the set up S 21.
19
mOT 2
3.4
Power supply of the accessories
13
14
15
16
-
+
Connection of the safety devices requires the use of any
push-button or N.C. (normally closed) contact.
When there are several safety devices, they are connected
in series.
22
20
21
MOT 1
Connect the terminal board 13 and
14 to power the accessories.
The tension on top of the terminal
boards is up of the transformer.
If the input STOP
is not used,
put "0" in the set up S15