9 - SELF-LEARNING OF WORKING TIMES
This menu allows the automatic learning of the times necessary to open and close the gate.
During this phase, the control unit memorizes also the forces necessary to open and close the gate: these values will be
activated by using the obstacle sensor.
CAUTION: to perform the self-learning procedure it is necessary to disable the ADI interface by means of the menu i.Adi .
If some safeties are controlled by means of the ADI module, they will not be active during the self-teaching stage.
CAUTION: ATTENTION: before proceeding, make sure to position the mechanical stops and the limit sensors correctly.
1. Press and hold the OK key until the display shows -APP
2. Release the OK key: the display shows ESC (only press the OK key if it is desired to exit this menu)
3. Press the i key: the display shows t.LAv
4. Press the OK key to activate the working time self-training cycle: the display shows the control panel and starts the time self-training
procedure.
4.1
The gate will be activated in closing direction until the stop end or the closing end of stroke is reached
4.2
The gate will be activated in opening direction until the stop end or the opening end of stroke is reached
4.3
The gate will be activated in closing direction until the stop end or the closing end of stroke is reached
CAUTION: during self-learning stage of times, the motor moves at reduced speed.
5. If the AMPEROMETRIC obstacle sensor was enabled, the display shows the suggested value for sensor threshold.
If no operations are performed for 20 seconds, the control unit exits the programming phase, without saving the value recommended.
6. The recommended value may be modified by pressing the
display shows SEn.A
7. Press and hold the i key until the display shows FinE, then press the OK key, select the option Si and then press the OK key to exit
programming mode, storing the value for the sensors.
PLEASE NOTE: If the control unit is left to time out from programming mode (1 minute), the obstacle sensor return to
the value that was set prior to performing self-training (according to the default values, the sensor is disabled).
On the other hand, the limit switch positions are always stored.
and i keys, and pressing the OK key confirms the displayed value and the