Wiring of control cables
Danger!
Switch off power supply before connecting or disconnecting terminals.
1.5 mm
max.
2.5 mm
Operating via control signals
D1
X13
X12
n
Start
E
X11
1
Start cw:
start clockwise
Start ccw:
start anticlockwise
VDC out:
voltage outputs
E:
Enable
Start drive via control signals:
 After Setup switch on start signals on X11.4 (start
clockwise) or X11.5 (start anticlockwise). The drive is
accelerated to 3.50 Hz (default value of P418).
Before commissioning, all covers must be mounted on the frequency inverter.
In case of errors refer to section "Error messages and warnings".
In case of wrong direction of rotation exchange two motor phases (e.g. U and V).
Note
For the default functions of all control terminals refer to section "Functions of control terminals".
05/2019
 Use shielded control cables.
 Connect the conductor shielding of the control cables to ground potential
by means of the shielding clamp.
 Connect the conductor shielding to ground potential on both sides of the
cable. Analogue cables must be grounded only on the inverter side.
 The control cable must be separated from the motor cable and mains cable
(not in the same cable duct).
X13
X12
2
X11
2
2 3
4
> 4k7
3
3 4 5
Operating via Operator panel
D2
X13
X12
E
X11
1
3
E: Enable
Start drive via key of operator panel
 After Setup select function Motorpoti (menu Lo-
cal/ Poti F, refer to section „Menus and func-
tions").
 Press RUN.
 The drive is accelerated to 3.50Hz
(default value of P. 418).
 Press the arrow keys to the speed.
39
3
Agile
Quick Start Guide