Setup via operator panel
 Switch on enable signals on X11.3 and X13.3.
 Switch off start signals on X11.4 and X11.5.
 Switch on mains supply.
 Start Setup procedure.
Caution!
If the motor data is not entered correctly, the drive may be damaged.
Start drive via control signals or via key of operator panel.
Agile
Quick Start Guide
Setup can be selected via menu item "Setup". At first switch-on Setup is
displayed automatically.
   
Complete Setup. Select for the first commissioning.
    
Select for only motor data measuring.
Select for commissioning of communication.
    
   
Data set query is only displayed if Setup is manually selected
via the menu item "Setup".
Choose data set 0. Another setting is only necessary for setup of various
motors.
   
Control method

Asynchronous motor
  
Asynchronous motor
  
Synchronous motor
Motor type plate (example)
V
Hz kW
A
230/400
50 0.25
1.32-0.76
   
  
  
    
Press for 1 s to increment or decrement each digit separately.
Entry of cosPhi in control method UF and Foc. Entry of PoLPrS (number
of pole pairs) in control method Synch.
Additional adjustments during commissioning setup):
Temperature evaluation at X12.4 via thermal contact, PTC, KTY,
PT100
Stopping behavior. Coast to stop, stop and switch off, emergency
stop and more
Function for energy saving
PID controller for process control
Electronic gear. Synchronization of drives.
See operating instructions.
Possible displays during commissioning (setup)
  
Message if Enable is missing. Switch on the signal at X11.3 and X13.3.
In case of error messages refer to section ". Error messages and
   
warnings during Setup".
   
Select, if further motor parameters are to be measured automati-
  
cally.
   
Measurement of motor data.
Select, if the data of a BONFIGLIOLI motor entered.
  
The pre-settings of other motor data are loaded.
Acceleration clockwise, factory setting 5Hz/ s
 
Deceleration clockwise, factory setting 5Hz/ s
 
Minimum frequency, factory setting 3.5Hz

Maximum frequency for speed limitation, factory setting 50Hz
 
Commissioning (Setup) completed and ready for use.
 
40
V/f-control with variable speed (default)
Field oriented control. High drive Dy-
namics and accurate speed control and
torque control.
cos 
min
-1
1375
0.77
   
   