AGL402 (3.0 ... 11.0 kW, 400 V)
CAUTION
Device defect and motor defect
The recommended motor shaft power indicated in the technical data applies to IE1
motors only. Ignoring the possible DC-link currents may decrease the motor product
life and may damage the inverter.
Type
Agile
402
Size
Output motor side
Recommended motor shaft
power
Output current
Long-term overload
current (60 s)
Short-time overload
current (1 s)
Switching frequency
Output, brake resistor
Minimum brake resistor
Recommended brake resis-
tor (770 V)
Input mains side
Rated current
Maximum mains current
Fuses
Fuses UL type
Mechanics
Dimensions
2)
Weight (approx.)
Degree of protection
Terminals
Installation
Interior fan
Heat sink fan
Ambient conditions
Power dissipation (2 kHz
switching frequency)
1) According to DIN EN 61800-5-1.
2) Dimensions of the basic device.
05/2019
Always verify the applicable operation parameters with regard to the par-
ticular motor type and inverter type combination.
Adapt software parameters if necessary.
P
kW
I
A
I
A
I
A
f
kHz
R
Ω
R
Ω
I
A
1)
I
A
I
A
I
A
HxWxD mm
m
kg
-
-
A
mm
2
-
-
-
-
-
-
P
W
-15
-18
-19
2
3.0
4.0
5.5
7.5
9.5
13.0 17.0 13.0 17.0 20.0 23.0
11.2
14.2 19.5 25.5 19.5 25.5 30.0 34.5
15.0
19.0 26.0 34.0 26.0 34.0 40.0 46.0
2, 4, 8, 16
106
106
48
148
106
80
6.8
7.8
14.2 15.8 14.2 15.8 20.0 26.0
9.8
12.8 17.2 23.0 17.2 23.0 28.1 33.6
10
10
16
Bussmann
FWP-20A14Fa
200 x 80 x 196
1.5
IP20 (EN60529)
Mains and motor
terminals:
Terminals relay out-
put:
133
167
235 321 235 321
53
400 V, 3-phase
-21
-19
-21
-22
3
7.5
5.5
7.5
9.2 11.0
48
48
48
48
58
80
58
48
25
16
25
25
Bussmann
FWP-30A14Fa
200 x 125 x 205
3
0.2 ... 4 (flexible with sleeve)
0.2 ... 6 (rigid)
0.1 ... 1.5
vertical
yes
yes
393 470
Quick Start Guide
-23
48
48
35
Agile

Publicidad

Tabla de contenido
loading