Technical Data Of Control Terminals - BONFIGLIOLI Vectron Agile Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Technical data of control terminals

CAUTION
Device damage
The digital inputs and the DC 24 V terminal of the electronic control equipment can
withstand external voltage up to DC 30 V. Higher voltages may destroy the unit.
Voltage
X11.1
DC 24 V, Imax =100 mA. Appropriate GND: X11.2.
X13.4
DC 10 V, Imax =2.3 mA (dependent on level of DC 24 V voltage input), Imax = 8.2 mA
outputs
Input for external voltage supply. Connect the ground potential of the external voltage sup-
X13.1
ply to X13.2 (GND).
Input voltage range
Voltage
Rated input current
inputs
Peak inrush current
External fuse
Safety
X11.3
Signal levels
Digital
X13.3
U
max
enable in-
Input Resistance
puts
Response time
X11.4
Signal levels
X11.5
Digital
X12.1
U
max
inputs
X12.2
Input resistance
Response time
PLC compatible
X11.6
X12.3
X12.4
X13.5
U
out
Digital
I
max
outputs
X11.6
 Digital input/ output
Analogue
X12.3
X12.4
inputs
Default: digital input. —► Refer to table row "Digital inputs".
X11.6
Digital in-
Can be configured as digital output by means of P558.
put/
Output:
output
Overload- and short circuit-proof, overvoltage- protected.
Agile
Quick Start Guide
Use suitable external power supply units with a maximum output voltage
of DC 30 V or use appropriate fuses to protect the unit.
The temperature monitoring must be sufficient insulated towards the
motor winding.
DC 24 V ± 10%
Max. 1.0 A (typical 0.45 A)
Typical < 15 A (max. 100 s)
Via standard fuse element for rated current, characteristic: slow
Safety extra low voltage (SELV) according to EN 61800-5-1
Low DC 0 ... 3 V, High DC 12 ... 30 V
DC 30 V (10 mA at DC 24 V)
1.8 k
STO is activated 10 ms after triggering.
PNP input
NPN input
DC 30 V (6 mA at DC 24 V)
3.9 k
2 ms
Digital input/ output
Multifunction
Multifunction
DC 22 V (DC 15 ... 30 V)
100 mA (I
max
Overload- and short circuit-proof, overvoltage- protected.
Multifunction
Multifunction
U
DC 22 V (DC 15 ... 30 V)
out
I
100 mA (I
max
High ≥ DC 10 V
High ≤ DC 5 V
is reduced if further control outputs are used.)
is reduced if further control outputs are used.)
max
54
Switch-over PNP/ NPN
X11.4
P559
X12.3
P452
X11.5
X12.4
P562
X12.1
X12.2
X11.6
05/2019

Publicidad

Tabla de contenido
loading

Tabla de contenido