5. Commissioning, operation
5.2.3
Requirements for shielding and grounding
Only use shielded cables and connect the shield on one side to the read-out unit.
The transmitter must be grounded via the process connection.
Ensure that no earth circuits can occur.
In case of Modbus
®
termination resistor at the physical start and end of the bus. The resistor can be activa-
ted via the software in the transmitters while at the gateway it is inserted mechanically
between A and B.
5.2.4
RS-485
The physical layer for the Modbus
TIA-485. The differential signal between pins 4 and 5 (A and B) is evaluated with a 2-wire
system (half-duplex). The mutual reference potential for the signals is on pin 1 (C).
5.3 Modbus
The Modbus
communication protocol is based on a master/slave architecture.
®
The protocol implemented in the model GDT-20 and model GDHT-20 transmitters is
Modbus
RTU with serial transmission via a 2-wire RS-485 interface.
®
The Modbus
protocol is a single-master protocol. This master controls the entire data
®
transfer and monitors any possible timeouts (no reply from the addressed instrument).
The connected instruments may only send telegrams after request by means of the
master.
Modbus
RTU (RTU: Remote Terminal Unit) transmits the data in binary form, guaran-
®
teeing a good data throughput.
Detailed information on the protocol under www.Modbus.org
5.4 Modbus
start-up kit
®
The transmitter with the optionally available startup kit (order no. 14075896) can be
configured at the measuring location for operation.
A further function is an integrated data logger, showing measured data in a specific
cycle or writing it in a file.
The start-up kit consists of:
Power supply unit
Interface converter (RS-485 to USB)
USB cable type A to type B
Sensor cable with M12 x 1 connector
Adapter cable for GDM-100-TI
Modbus
tool
®
WIKA operating instructions transmitter, models GDT-20 and GDHT-20
communication issues, it is recommended to install the 120 Ohm
protocol is the serial RS-485 interface per EIA/
®
EN
35