Electrical Connection - Sime Format Dewy.zip 25 BF Manual De Instrucciones

Ocultar thumbs Ver también para Format Dewy.zip 25 BF:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 25
2. 1 0
POSITIONING THE
OUTLET TERMINALS
The outlet terminals for forced-draught
appliances may be located in the external
perimeter walls of the building.
To provide some indications of possible solu-
tions, Table 3 gives the minimum distances
to be observed, with reference to the type
TABLE 3
Siting of terminal
A - below openable window
B - below ventilation opening
C - below eaves
D - below balcony (1)
E - from adjacent window
F - from adjacent ventilation opening
G - from horizontal or vertical soil or drain pipes (2)
H - from corner of building
I - from recess in building
L - from ground level or other treadable surface
M - between two terminals set vertically
N - between two terminals set horizontally
O - from a surface facing without openings or terminals
P - as above but with openings and terminals
1) Terminals below a practicable balcony must be located in such a way that the total path of
2) When siting terminals, where materials that may be subject to the action of the combu-
of building shown in fig. 13.
2. 1 1

ELECTRICAL CONNECTION

The boiler is supplied with an electric cable.
Should this require replacement, it must be
purchased exclusively from SIME.
The electric power supply to the boiler must
the smoke from its outlet point from the terminal to its outlet point from the external peri-
meter of the balcony, including the height of possible railings, is not less than 2000 mm.
stion products are present in the vicinity, e.g., eaves, gutters and downspouts painted or
made of plastic material, projecting timberwork, etc., distances of not less than 1500 mm
must be adopted, unless adequate shielding is provided to guard these materials.
be 230V - 50Hz single-phase through a
fused main switch, with at least 3 mm spa-
cing between contacts. Respect the L and N
polarities and the earth connection.
NOTE: SIME declines all responsibility for
injury or damage to persons, animals or
things, resulting from the failure to provi-
de for proper earthing of the appliance.
Appliances from 7 to 35 kW
(distances in mm)
600
600
300
300
400
600
300
300
300
2500
1500
1000
2000
3000
IT
ES
PT
GB
RUS
Fig. 13
77

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Format dewy.zip 30 bf

Tabla de contenido