13.2.7 Supply voltage
3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE.
The supply voltage and frequency are marked on the pump
nameplate. Make sure that the motor is suitable for the power
supply of the installation site.
The wires in the terminal box must be as short as possible.
Excepted from this is the protective ground lead which must be so
long that it is the last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
Torques, terminals L1-L3:
Min. torque: 1.6 ft-lbs (2.2 Nm)
Max. torque: 1.8 ft-lbs (2.4 Nm)
Fig. 15 Power connection
Cable glands
Cable glands comply with EN 50626.
•
1 x M40 cable gland
•
1 x M20 cable gland
•
2 x M16 cable gland
•
2 x M16 knock-out cable entries.
DANGER
Electric shock, malfunction or damage
Death or serious personal injury; product damage or
failure
- Replace power supply cable immediately if
damaged.
- Only qualified personnel must replace it.
Grid types
Three-phase E-pumps can be connected to all grid types.
DANGER
Electric shock
Death or serious personal injury; product damage or
failure
- Do not connect three-phase E-pumps to a power
supply with a voltage between phase and ground
of more than 440 V.
All manuals and user guides at all-guides.com
13.2.8 Start/stop of pump
When the pump is switched on via the power supply, it will start
after approx. 5 seconds.
If a higher number of starts and stops is desired, use the input for
external start/stop when starting/stopping the pump.
When the pump is switched on via an external On/Off switch, it
will start immediately.
13.2.9 Connections
As a precaution, the wires to be connected to the following
connection groups must be separated from each other by
reinforced insulation in their entire lengths:
Group 1: Inputs
•
•
•
•
•
All inputs (group 1) are internally separated from the power-
conducting parts by reinforced insulation and galvanically
separated from other circuits.
All control terminals are supplied with protective extra-low voltage
(PELV), thus ensuring protection against electric shock.
Group 2: Output (relay signal, terminals NC, C, NO)
The output (group 2) is galvanically separated from other circuits.
Therefore, the supply voltage or protective extra-low voltage can
be connected to the output as desired.
The number of starts and stops via the power supply
must not exceed 4 times per hour.
If no external On/Off switch is connected, connect
terminals 2 and 3 using a short wire.
start/stop
terminals 2 and 3
digital input
terminals 1 and 9
setpoint input
terminals 4, 5 and 6
sensor input
terminals 7 and 8
GENIbus
terminals B, Y and A
25