3 Technical description
3.4.7
3.5
Characteristic
IPG 40K
Recommended
40 kW
p
solar generator
connected load
Output power
36 kW
Efficiency factor,
95.2%
maximum
Efficiency factor,
94.5%
European standard
Input voltage range
MPP range for
nominal DC
capacity
Input current
81 A
DC
Grid voltage range
196 to 253 V (standard setting), can be adjusted to other countries' standards
(phase to N)
Grid frequency
49.8 to 50.2 Hz (standard setting), can be adjusted to other countries' standards 49.8 to 50.2
range
Output in stand-by
43 W
mode
Output in night
43 W
mode
Distortion factor of
the output current
AC output
L1, L2, L3, N and PE,
connection
one terminal per pole
terminals
DC inputs
18
LED display
Four LED indicators, marked On, SG, Grid and Fault are built into
the front door.
3–4:
Front door LED display
Display
Meaning
On
Grid feed-in mode
SG
Status of solar generator voltage and output
Grid
Status of grid connection
Fault
Malfunction indicator
Specifications
IPG 60K
IPG 80K
IPG 100K
60 kW
80 kW
100 kW
p
p
54 kW
72 kW
90 kW
95.2%
96,5%
96,5%
94.2%
96.0%
96.2%
Vpmin = 493 V
/Vocmax = 965 V
DC
493 V
to 780 V
.
DCMin
122 A
162 A
203 A
DC
DC
43 W
49 W
49 W
43 W
49 W
49 W
< 2%
L1, L2, L3, N and PE, 2 M12 pins per pole
3
Operating manual
IPG 110K
IPG 280K
110 kW
280 kW
p
p
100 kW
250 kW
96,5%
95.6%
96.2%
94.6%
DC
DC
223 A
568 A
DC
DC
DC
49 W
55 W
49 W
55 W
4
Conergy IPG series central inverters
Fault
IPG 300K
300 kW
p
p
270 kW
97%
96.5%
Vpmin = 530
V
/Vocmax =
DC
965 V
DC
530 V
to
.
DCMin
780 V
DC
566 A
DC
126 to 179 V
Hz
55 W
55 W
< 3%