Restoration; Disposal; Technical Data - GOK BC-2 Instrucciones Para El Montaje Y El Funcionamiento

Proteccion contra sobrellenado
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 96

RESTORATION

If the actions described in MAINTENANCE do not lead to a proper restart and if there is no
dimensioning problem, the product must be sent to the manufacturer to be checked. Our
warranty does not apply in cases of unauthorised interference.
In case of a constant alarm indication without the probe part coming into contact with liquid,
check the connection lines and signal and probe part for disconnection or short circuit and re-
assemble if necessary.

DISPOSAL

To protect the environment, our electrical and electronic appliances may not
be disposed of along with household waste.
The commercial customer (owner) is obligated to properly dispose of the electronic
devices of the "GOK" brand delivered to them at their own expense in accordance
with the provisions in the Elektro- und Elektronikgerätegesetz (ElektroG) [Electrical
and Electronic Equipment Act] after termination of the use thereof. In this way, GOK
Regler- und Armaturen-Gesellschaft mbH & Co. KG is exempt from the obligations
under Sec. 10 para. 2 ElektroG and third-party claims connected thereto.
If the commercial customer fails to contractually obligate third parties to whom they
forward our electronic devices to assume the disposal obligation and to pass on
obligations, this customer shall be obligated to take back the supplied electronic
devices at their own expense and to properly dispose of them in accordance with the
statutory provisions after termination of the use thereof.
Our registration number for the electrical old appliances register (EAR) is:
WEEE-Reg.-No. DE 78472800.

TECHNICAL DATA

Indicator
Supply voltage
Power consumption
Voltage tolerance
Protection type
Housing
Dimensions H x W x D
Sound level of alarm sound:
Action
Probe
Materials
Installation position:
Voltage:
Probe length
Length of the probe tube diameter
Diameter of sensor cover
Temperature of the operating media
Ambient temperature
The BC-2 is a regulating and control system (RS) of over-voltage category III,
Rated impulse voltage 4000V, contamination degree 2 according to EN 60730-1.
Protection class type 2
Artikel-Nr. 15 707 50
230V AC; 50-60Hz
4.5VA
+10% / -10%
IP54 acc. to EN 60529
Polycarbonate
194 x 130 x 65mm
≥ 70dB(A)
Typ 1.B (according to EN 60730-1)
1.4301 ; 1.405 ; PA (depending on the version)
vertically upright
12V DC
Z = 150 to 1000mm
10 mm
18 mm
-25°C to +60°C
-20°C to +60°C
BC-2
35 / 133

Publicidad

Tabla de contenido
loading

Tabla de contenido