Checks; Checking The Combustion Parameters; Shutdown; Temporary Shutdown - Sime ESTELLE HE 3 ErP Manual De Uso, Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7.2.1

Checks

After the start-up, check that the ESTELLE HE ErP boiler per-
forms a lock-out and switches back on. To do this:
– modify the calibration of the heating thermostat
– adjust the room thermostat or the time programmer
– check that the system pump is working
– check that the boiler locks out completely by shifting the sys-
tem's main switch and the device's main switch to "off".
If all the conditions are fulfilled, restart the boiler, bring it to full
power and analyse the combustion by-products.
7.3

Checking the combustion parameters

After running the boiler at full power, to conduct the combustion
checks it is necessary to connect a fume analyser and a fume
thermometer to the withdrawal socket (1), as illustrated in the
figure.
Then measure:
– CO
(%)
2
– CO (ppm) (as per the regulations in force)
– Bacharach index (≤ 0,5)
– Fume temperature
Check that the measured values are very close or equal to the
values of the technical data table. If not, correct the regulations
made.
m
WARNINGS
– In certain countries, the regulations in force require
measuring the combustion performance.
88
1
Fig. 38
7.4

Shutdown

7.4.1

Temporary shutdown

If the user is away temporarily, for a weekend, short trip etc and
if the outside temperature is at ZERO:
– press the main switch (6) to switch off the boiler
– close the fuel and water circuit shut-off valves.
7.4.2

Shutting down for long periods

If the boiler is to be left unused for a long period, the following
operations need to be carried out:
– press the main switch (6) to switch off the boiler
– close the fuel and water circuit shut-off valves
– set the main system switch to "OFF"
– drain the system if there is the risk of freezing.
OFF
m
CAUTION
In case of difficulties in completing the described pro-
cedure, contact professionally qualified personnel.
EN
6
1
0
Fig. 39
Fig. 40
Fig. 41