The above assignment of the functions to the control terminals is
the default setting of parameter
410. The functions can be assigned to the control terminals as
required. For more configurations, refer to the Operating Instruc-
tions.
Digital inputs (X210A.3 ... X210B.3): Low Signal: DC 0 V ... 3 V, High signal: DC 12 V
... 30 V,
Input resistance: 2.3 kΩ, response time: 2 ms (STOA and STOB: 10 ms), PLC compati-
ble
Digital output MF3 (X210B.3): Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ...
30 V,
Maximum output current: 50 mA, PLC compatible
Multifunction input/output MF2 (X210B.4):
Digital input: Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V, max. output
current: 50 mA, PLC compatible
Digital output: Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V, PLC compatible
Analog output: DC 19 ... 28 V, maximum output current: 50 mA, pulse-width modulat-
ed (f
= 116 Hz),
PWM
Frequency signal: Output voltage: DC 0 V ... 24 V, maximum output current: 40 mA,
maximum output frequency: 150 kHz
Multifunction input MF1 (X210B.6):
Analog signal: Input voltage: DC 0 ... 10 V /±10 V (R
20 mA (R
=249 Ω),
i
Digital signal: Low Signal: DC 0 V ... 3 V, High signal: DC 12 V...30 V, response time: 4
ms, PLC compatible
Conductor cross-section:
The signal terminals are suitable for the following cable sizes:
with ferrule:
0.25 ... 1.0 mm²
without ferrule: 0.14 ... 1.5 mm²
4.3.2
External 24 V power supply X210A.1 & X210A.2
NOTICE
Device damage possible
The digital inputs and the DC 24 V terminal of the electronic
control equipment can withstand external voltage up to DC 30 V.
Higher voltages may destroy the unit.
Avoid higher voltage levels.
Use suitable external power supply units with a maximum
output current of DC 30 V or use appropriate fuses to protect
the unit.
07/20
Technical data of control terminals
Quick Start Guide ANG
30 to value 110 or
Configuration
=73,5 kΩ), Input current: DC 0 ...
i
GB
107

Publicidad

loading

Este manual también es adecuado para:

Vectron ang410Vectron ang510Vectron ang610