Line choke
Line chokes reduce mains harmonics and reactive power. In addition, a longer
service life of the frequency inverter is possible. When using a line choke, note
that line chokes may reduce the maximum output voltage of the frequency
inverter. The line choke must be installed between the mains connection and
the input filter.
Input filter
Input filters reduce grid-bound, high-frequency radio interference voltage.
Install input filter on the mains side upstream of the frequency inverter.
The frequency inverters meet the requirements of the low-voltage
directive 2006/95/EC and the requirements of the EMC directive
2004/108/EC. The EMC product standard EN 61800-3 relates to
the drive system. The documentation provides information on how
the applicable standards can be complied if the frequency inverter
is a component of the drive system. The declaration of conformity
is to be issued by the supplier of the drive system.
4.2
Connection
4.2.1
ANG210 (up to 3.0 kW) and 410 (up to 4.0 kW)
Mains connection, X1
1
With a mains current above 10 A, the mains power connection 230 V
1ph/N/PE and the mains power connection 230 V 2ph/N/PE are to be done on
two terminals.
07/20
Quick Start Guide ANG
GB