For release of the output stage, wiring of digital inputs S1IND (STOA)
and S7IND (STOB) is required.
Confirm the final "rEAdY" message by pressing the
•
ENT key.
Cancelling the operation with the ESC key or withdrawing
the enable signal S1IND (STOA) or S7IND (STOP) results
in an incomplete take-over of the values.
In the case of more demanding requirements regarding the accuracy
of the speed/torque control, you should carry out the guided commis-
sioning procedure once again under operating conditions because part
of the machine data depends on the operating temperature.
During this procedure, confirm the rated machine values already
•
entered.
Confirm the "End" display by pressing the ENT key.
•
The guided commissioning of the frequency inverter is ter-
minated via a reset and the initialization of the frequency
inverter. The relay output X10 signals a fault.
After successful initialization of the frequency inverter, the
factory-set parameter
The drive is accelerated to the set
(default 3.50 Hz) by:
Signals at digital inputs S1IND (STOA) and S7IND
−
(STOB) and
Start clockwise by rising signal edge at S2IND or Start
−
anticlockwise by rising signal edge at S3IND
07/20
Actual Frequency
Min. frequency
Quick Start Guide ANG
241 is displayed.